4.4 Stopping the engine in manual mode
Preconditions
☑
Engine not under load.
☑
Engine in manual mode.
NOTICE
Stopping the engine when it is running at full load subjects it to extreme thermal and mechanical
stresses.
Overheating of and, therefore, damage to components is possible!
• Before shutting down the engine, allow it to idle until the engine temperatures decrease and
constant levels are indicated.
Preparations
Item
Action
Engine
Run engine at idling speed under zero load.
Stopping the engine
Item
Action
Switchgear cabinet, control
panel etc. (depending on
manufacturer)
Press stop button.
•
Automatic stopping sequence is executed.
•
If the coolant temperature is too high, the engine runs on automatical-
ly for up to 3 minutes.
MS15042/00E 2014-10
| Operation | 39