C
Night function speed in chiller mode.
Used to set a maximum value of the proportional control of the
fans in chiller mode.
Expressed as a percentage from 0 to 100% of the maximum
permitted voltage.
0
100
%
Operation in heat pump mode
FA16
C
Fans minimum speed in heat pump mode.
Used to set a minimum value of the proportional control of the
fans in heat pump mode.
Expressed as a percentage from 0 to 100% of the maximum
permitted voltage.
0
100
%
FA17
C
Fans maximum speed in heat pump mode.
Used to set a maximum value of the proportional control of the
fans in heat pump mode.
Expressed as a percentage from 0 to 100% of the maximum
permitted voltage.
0
100
%
FA18
C
Proportional control:
Fans maximum speed temperature / pressure set in heat pump
mode.
Used to set the condensing temperature / pressure value in heat
pump mode corresponding to the minimum fan speed.
Step control
1st STEP SET
Used to set the condensing temperature / pressure
value in heat pump mode to which operation in ON corresponds
of the relay output configured as 1st condensing fan speed step.
0.0
0
50.0
725
Bar
Psi
Dec
Int
FA19
C
Proportional control:
Fans minimum speed temperature / pressure set in heat pump
mode.
Used to set the condensing temperature / pressure value in heat
pump mode corresponding to the maximum fan speed.
Step control
2nd STEP SET
Used to set the condensing temperature / pressure
value in heat pump mode to which operation in ON corresponds
of the relay output configured as 2nd condensing fan speed step.
0.0
0
50.0
725
Bar
Psi
Dec
Int
FA20
C
Proportional control:
Fans proportional band in heat pump mode.
Used to set a temperature / pressure differential with a
corresponding change in fan speed from minimum to maximum.
Step control
With Par.
FA01
= 2 or 3 this becomes the differential on the step
of circuit 1 in heat pump mode (see fans control diagram).
0.1
1
14.0
203
Bar
Psi
Dec
Int
FA21
C
Proportional control:
CUT-OFF differential in heat pump mode.
Used to set a temperature / pressure differential in heat pump
mode for stopping of the fan.
Step control
With Par.
FA01
= 2 / 3 becomes the differential on the step of
circuit no. 2 in heat pump mode (see fans control diagram).
0.1
1
14.0
203
Bar
Psi
Dec
Int
FA22
C
CUT-OFF override in heat pump mode.
Used to set a temperature / pressure differential in heat pump
mode at which the fan remains at minimum speed.
0.1
1
14.0
203
Bar
Psi
Dec
Int
FA23
C
Night function speed in heat pump mode.
Used to set a maximum value of the proportional control of the
fans in heat pump mode.
Expressed as a percentage from 0 to 100% of the maximum
permitted voltage.
0
100
%
Hot start
FA24
C
Hot start setpoint.
-50.0
-58
110.0
230
°C
°F
Dec
Int
FA25
C
Hot start differential.
0.1
0
25.0
45
°C
°F
Dec
Int