Chapter 7 - Electronic controller
TAEevo Tech 015÷802 60 Hz UL
77
The data in this manual are not binding and they can be modified by the manufacturer without notice.
Reproduction of this manual is strictly prohibited
EN
ENGLISH
CF50
C
Proportional output OUT 1:
0= Output disabled
1= Evaporator pump 0...10V with modulating operation
2= Modulating output 0...10V for Free cooling
3= Not used
4= 0...10V auxiliary output no. 1
5= 0...10V auxiliary output no. 2
6= 0...10V modulating output compressor 1 circuit no. 1
7= 0...10V modulating output compressor 1 circuit no. 2
8= Condensing fans 0...10V modulating output circuit no. 1
9= Condensing fans 0...10V modulating output circuit no. 2
Relay controlling ON / OFF output
0
o 1
9
c50
CF51
C
Proportional output OUT 2:
0= Output disabled
1= Evaporator pump 0...10V with modulating operation
2= Modulating output 0...10V for Free cooling
3= Not used
4= 0...10V auxiliary output no. 1
5= 0...10V auxiliary output no. 2
6= 0...10V modulating output compressor 1 circuit no. 1
7= 0...10V modulating output compressor 1 circuit no. 2
8= Condensing fans 0...10V modulating output circuit no. 1
9= Condensing fans 0...10V modulating output circuit no. 2
Relay controlling ON / OFF output
0
o 1
9
c50
CF52
C
Proportional output OUT 3:
0= Output disabled
1= Evaporator pump 0...10V with modulating operation
2= Modulating output 0...10V for Free cooling
3= Not used
4= 0...10V auxiliary output no. 1
5= 0...10V auxiliary output no. 2
6= 0...10V modulating output compressor 1 circuit no. 1
7= 0...10V modulating output compressor 1 circuit no. 2
8= Condensing fans 0...10V modulating output circuit no. 1
9= Condensing fans 0...10V modulating output circuit no. 2
10= Condensing fans phase chopping modulating output circuit
no. 1
11= Condensing fans phase chopping modulating output circuit
no. 2
Relay controlling ON / OFF output
0
o 1
11
c50
CF53
C
Proportional output OUT 4:
0= Output disabled
1= Evaporator pump 0...10V with modulating operation
2= Modulating output 0...10V for Free cooling
3= Not used
4= 0...10V auxiliary output no. 1
5= 0...10V auxiliary output no. 2
6= 0...10V modulating output compressor 1 circuit no. 1
7= 0...10V modulating output compressor 1 circuit no. 2
8= Condensing fans 0...10V modulating output circuit no. 1
9= Condensing fans 0...10V modulating output circuit no. 2
10= Condensing fans phase chopping modulating output circuit
no. 1
11= Condensing fans phase chopping modulating output circuit
no. 2
Relay controlling ON / OFF output
0
o 1
11
c50
Remote terminal
CF54
U
Configuration of remote terminal no. 1:
0= Absent
1= On board NTC probe
2= Without on board NTC probe
0
2
Parameter Level
Description
Min.
Max.
UM
Resolution