Section 9
ZGARD CX II Controller
Operation & Configuration Set Up Menu
36.
Once the link to the communication board is established, the CX-II will display the available user parameters
based on which communication board is plugged into the CX-II:
36.1.
MODBUS ASCII (SW1-1=OFF on MODBUS plug-in board):
S E R I A L I / O
T Y P E : M O D / A S C
B A U D : 1 1 5 2 0 0
A D D R S . : 0 0 1
F R A M E : 7 E 1
< , > : N X T / P R V
0 . . 9 : V A L U E
E N T E R : A C C E P T
36.2.
MODBUS RTU (SW1-1=ON on MODBUS plug-in board):
S E R I A L I / O
T Y P E : M O D / R T U
B A U D : 1 1 5 2 0 0
A D D R S . : 0 0 1
F R A M E : 8 N 1
< , > : N X T / P R V
0 . . 9 : V A L U E
E N T E R : A C C E P T
36.3.
BACnet:
S E R I A L I / O
T Y P E : B A C N E T
B A U D : 1 1 5 2 0 0
D E V . I D : 2 9 1 0 0 0
F R A M E : 8 N 1
M A C : 0 0 1
< , > : N X T / P R V
0 . . 9 : V A L U E
E N T E R : A C C E P T
36.4.
Go to next parameter
:
Press the
or
key to move through all of the desired parameters. Not all
parameters are changeable. Some are fixed based on type. A flashing value indicates that it may be
changed.
36.5. Using the numbers on the keypad, change the value of the flashing parameter
36.6. Press
ENTER
to save the parameter and move onto the next one.
37. Press the MENU key
38. The
ACCESS CODE
menu will appear. To change the Set-up Menu access code, type in a new code and
press ENTER. The access code can be up to 4 digits in length and consist of any combination of numbers
from 0 to 9.
A C C E S S C O D E
N E W C O D E :
1 2 3 4
0 . . 9
: V A L U E
E N T E R : A C C E P T
39. Press the MENU key.
40.
The menu system now repeats from the first menu (Auto-Config).
41.
To exit the configuration menu system at any time, press the RUN key.
9.7