Section 6
ZGARD CX II Controller
Serial I/O Feature & Operation
BACnet:
All BACnet registers are read-only and
are intended for remote monitoring purposes only.
Writing to a register is not permitted.
BACnet Object Table:
Analog:
1
– 99: Gas Value, Sensor 1 – 99
101
– 199: Gas Range, Sensor 1 – 99
201
– 299: Caution Setpoint, Sensor 1 – 99
301
– 399: Warning Setpoint, Sensor 1 – 99
401
– 499: Alarm Setpoint, Sensor 1 – 99
501
– 508: High Select, Zone 1 – 8
511
– 518: No. Sensors, Zone 1 – 8
Multi-State:
101
– 199: Alarm State, Sensor 1 – 99
201
– 299: Zone Assignment, Sensor 1 – 99
301
– 399: RS-485 Port, Sensor 1 – 99
401
– 499: GasID, Sensor 1 – 99
Binary:
1
– 40: Relay Status, Relay 1 – 99
BACnet Baud Rate:
The BACnet baud rate is
selectable from the configuration menu (see page
9.7). Available choices are: 9600, 19200, 38400,
57600 and 115200 BAUD.
BACnet MAC Address:
The BACnet MAC address
is selectable from 1-255 in the configuration menu
as well (see page 9.7).
BACnet Device ID:
The BACnet Devide ID is
selectable from 291000-291999 in the configuration
menu as well (see page 9.7).
6.1