Ultima MOS-5 Detector
41
8.8 Ultima MOS-5 Command Register Details
8.8.1 Analog
(00H)
A read returns a value, which is proportional to the 0-20 mA output current. The current is
based on a 16-bit value. The scaling is 0 - 65535 decimal, which corresponds to 0 - 21.7 mA.
8.8.2 Mode
(01H)
A read returns the present mode of the Ultima MOS-5 Intelligent Sensor.
A write command changes the mode to the requested mode. A data value of 08 starts
calibration mode if the unit is in the run mode. It also goes from cal check to cal mode.
Exception: Returns an exception code 01 (illegal function) if an illegal write is requested.
A calibrate command returns an exception code 01 (Acknowledge 05). The operation will take
a long time to complete.
Function
Bit Position
Access
Calibration Complete
7 MSB
Read
Spanning 6
Read
Zero Complete, Waiting for Gas
5
Read
Zeroing 4
Read
Calibration Mode
3
Read/Write
Calibration Check Mode
2
Read/Write
Run Mode
1
Read
Startup Mode
0 LSB
Read
8.8.3 Status/Error
(02H)
A read returns the alarm state and errors that are occurring at the present time, which are
indicated, by bit position.
Function
Bit Position
Access
Alarm 15
MSB
Read
Warn 14
Read
Fault 13
Read
Not Used
12
Read
Not Used
11
Read
Not Used
10
Read
Not Used
9
Read
Switch Error
8
Read
Setup Error
7
Read
Calibration Check Timeout
6
Read
EEPROM Error
5
Read
EPROM Error
4
Read
Sensor Error
3
Read
Fail to Calibrate
2
Read
Low Supply Voltage
1
Read