Calibration Settings
Bump Check Procedure
A bump check verifies the sensor response to a known concentration of gas. The recommended equip-
ment for a Bump Check is the HART Calibration Cover/Bump Cap (P/N 10122228). A known concen-
tration of gas should be supplied to the inlet port of the Bump cap and compared to the gas value on
the output signal (see Fig. 10). Alternately, if using the environmental guard to perform a bump check
the gas should be delivered to both ports of the environmental guard from a 1.5 l/min regulator. Use
PrimaX IR Calibration Kit #55 for the tubing, regulator and Remote HART screens shown below.
Target Gas
Range
% LEL
ATEX
performance
certified
Calibration
Gas
Span
Value %
LEL
t50
t90
Gas Curve
Number
Methane
0-100
Yes
2.5%v/v Methane
57
12 s
22 s
1
Propane
0-100
Yes
0.6%v/v Propane
35
10 s
25 s
2
Toluene
0-50
Yes
2.5%v/v Methane
57
11 s
28 s
3
n-Butane
0-100
Yes
0.6%v/v Propane
37
10 s
24 s
2
n-Pentane
0-100
Yes
0.55%v/v n-Pentane
50
11 s
24 s
2
n-Hexane
0-100
Yes
0.5%v/v n-Hexane
50
11 s
24 s
2
Propylene
0-100
Yes
1.0%v/v Propylene
50
11 s
25 s
3
Ethane
0-100
Yes
1.2%v/v Ethane
50
11 s
23 s
3
Propylene Oxide
0-100
Yes
2.5%v/v Methane
19
11 s
25 s
3
Acetone
0-100
Yes
2.5%v/v Methane
44
11 s
25 s
2
Cyclopentane
0-100
Yes
0.6%v/v Propane
35
10 s
25 s
2
Ethyl Acetate
0-100
Yes
2.5%v/v Methane
21
12 s
25 s
2
IsoButane
0-70
Yes
0.65%v/v IsoButane
50
12 s
26 s
2
Ethylene
0-100
No
1.35%v/v Ethylene
59
10 s
23 s
3
Xylene
0-100
No
1.35%v/v Ethylene
19
10 s
25 s
3
1 Response time t50 and t90 with HART calibration cover, gas flow rate 1.5 l/min
2 IEC 60079-20-1 was used as bases for converting test and calibration gas concentrations from %
LEL to % volume fraction
3 For the measurement of n-Pentane, n-Hexane, Propylene, Ethane or Isobutane PrimaX IR shall be
calibrated with the target gas at a span value of approximately 50 % LEL.