12.3 Specifications
FS-ROUTER-BAC2
Electrical Connections
One 3-pin Phoenix connector with: RS-485/RS-232 (Tx+ / Rx- / gnd)
One 3-pin Phoenix connector with: RS-485 (+ / - / gnd)
One 3-pin Phoenix connector with: Power port (+ / - / Frame-gnd)
One Ethernet 10/100 BaseT port
Power Requirements
Input Voltage:
9-30VDC or 24VAC
Max Power:
3 Watts
Current draw:
24VAC 0.125A
9-30VDC 0.25A @12VDC
Approvals
CE and FCC Class B & C Part 15, UL 60950-1, WEEE compliant, IC Canada,
RoHS3 compliant, REACH compliant, UKCA compliant
Physical Dimensions
4 x 1.1 x 2.7 in (10.16 x 2.8 x 6.8 cm)
Weight
0.4 lbs (0.2 Kg)
Operating Temperature
-20°C to 70°C (-4°F to158°F)
Humidity
10-95% RH non-condensing
“This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
•
This device may not cause harmful interference
•
This device must accept any interference received, including interference that may cause undesired operation.
NOTE:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15
of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the
equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his expense.
Modifications not expressly approved by FieldServer could void the user's authority to operate the equipment under FCC
rules.”