Microwave Motion and
Presence Sensor Installation Instructions
MS Sedco INTERSECTOR Installation Instructions
Page Addendum-4
INTERSECTOR-1.9Uv092717
EXPLANATION OF CHANGES (CONTINUED)
Automated OZP (continued)
In addition to these
changes, the DBM timer
setting for a stopped
vehicle is now displayed
on the Zone Setting page,
in the Vehicle Table. When
a vehicle is stopped, its
classification field is
changed to the remaining
DBM timer value. Once the
vehicle speed is greater
than 0, the classification
field will switch back, as
shown in Figure 5.
Zone Clear Feature
The new Clear feature
allows the user to set
automatic timing for
clearing hung vehicles as
traffic begins to move. The
INTERSECTOR will track
vehicles as they begin to
leave the detection zones.
Once a vehicle has moved
10 feet past the front edge
of the zone, the value in
the “Set Clear Time” field
will begin counting down.
Any vehicles that did not
reach the “Clear Speed” once the front vehicle has departed will be cleared after the
timer has expired. Both the “Set Clear Time” and “Clear Speed” fields are configurable
on the Setup page, as shown in Figure 6. Default value for “Set Clear Time” is 1.0
seconds. Default value for “Clear Speed” is 2.0 mph. Ranges for these fields are from
0.0 to 10.0. To disable this feature, set “Set Clear Time” to 0.
Figure 5
Figure 6