23
Internal parameters table 2
Par
ame
ter
Parameter Name
Parameter
Function
Description
(Range)Factory
Value
LC
password
When Lc=3, it can view and
modify parameters
0
AL2
Second
set
over-temperatur
e alarm
When the "secondary set
temperature measurement ≥
second set temperature set
value + AL2", the heating
output is turned off.
( 0.~100. ℃ )
10.0
cT2 Second
set
compressor delay
Second set compressor delay
protection time
(0~60 minutes)
3
T-- heating control
cycle
heating control cycle
(1~60 seconds)
5
p-- heating
proportional
band
time
proportional
action
regulation
(1~rH℃)15
I-- heating integral
time
integral adjustment function (
1~1000
seconds)200
d-- heating calculus
time
differential
action
adjustment
(
1~1000
seconds)100
Pb2 second
set
zeroadjustment
correcting the error occurred
by the sensor measurement at
low temperature.
Pb2= actual value - meter
measurement
( — 99.9~99.9
℃)
0
PK2
second set
full-degree
adjustment
correcting the error occurred
by the sensor measurement at
high temperature.
PK2=1000* ( actual value -
meter measurement ) / meter
measurement
(—9.9~999)
0
rL
—
range
lower
limit
the lower limit of the
temperature measurement value
( — 150~0.0 ℃ )
—150
rH
range
upper
limit
the upper limit of the
temperature measurement value
(0.0~300℃)
300