8 Technical data
Maschinenfabrik Reinhausen GmbH 2020
63
4360571/02 EN
VACUTAP
®
VM
®
8.2 Technical data for protective relay
The technical data for the protective relay RS 2001 is listed in the following.
In accordance with DIN EN 60255-1, operational accuracy = base accuracy
Housing
Outdoor model
Degree of protection
IP66
Relay actuation
Flap valve with aperture
Weight
approx. 3.5 kg
Oil flow speed of available types when
tripping (oil temperature 20 °C)
0.65 ± 0.15 m/s
1.20 ± 0.20 m/s
3.00 ± 0.40 m/s
4.80 ± 0.60 m/s
Table 13: General technical data
Tripping circuit
The protective relay can be supplied with either a normally open (NO) or a
normally closed (NC) dry-reed magnetic switch (see dimensional drawing
supplied). Other contact combinations are available as a special version.
Electrical data for normally closed (NC) dry-reed magnetic switch
Electrical data
DC switching capacity
1.2 W…200 W
AC switching capacity (50 Hz)
1.2 VA…400 VA
Switching voltage AC/DC
24 V…250 V
Switched current AC/DC
4.8 mA…2 A
Table 14: Electrical data
Switching capacity (switching load on an off)
Minimum switched current AC/DC (low-
est voltage)
50 mA (at 24 V)
Minimum switched current AC/DC (high-
est voltage)
4.8 mA (at 250 V)
Maximum switched current DC (highest
current)
1.6 A (at 125 V with L/R = 40 ms)
Maximum switched current DC (highest
voltage)
0.9 A (at 250 V with L/R = 40 ms)
Maximum switched current AC (highest
current)
2 A (at 125 V with cos φ = 0.6)
Maximum switched current AC (highest
voltage)
1.6 A (at 250 V with cos φ = 0.6)
Switching operations
1,000 cycles
Table 15: Switching capacity (switching load on an off)
Summary of Contents for VACUTAP VM I 1002
Page 1: ...On load tap changer VACUTAP VM Operating Instructions 4360571 02 EN Selector size RC RD RDE ...
Page 69: ...9 Drawings Maschinenfabrik Reinhausen GmbH 2020 69 4360571 02 EN VACUTAP VM 9 Drawings ...
Page 70: ......
Page 71: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......