Basic operation
Function: Check number of alarms
Action
MLog display Home menu Alarm
Entries
Suggestion
Press „DISPLAY ON“
button longer than
2 seconds
Number of limit value exceedings
is displayed
If necessary, read the MLog data via the Analyser
software in order to analyse the alarms.
3.3
MLog IM100 status check via LED
Function: Check battery status
Action
LED
BATTERY (yellow)
Result
Suggestion
Press „DISPLAY
ON“ button longer
than 2 seconds; then
press „DISPLAY ON“
button shortly
5 seconds flashing
Battery status is „Low“;
Renew
batteries
off
Battery status is sufficient.
A prognosis of the remaining recording
duration can be called up via display or via
MLog Analyser.
Function: Check operation mode and memory status
Action
LED
Result
Suggestion
ACTIVE
(green)
EVENT/
ALARM(red)
Operation mode
Memory status
Press „DISPLAY
ON“ button longer
than 2 seconds; then
press „DISPLAY ON“
button shortly
lights
3 seconds
off
ready for recording
Memory empty
lights
3 seconds
lights
3 seconds
no recording
Log book in memory
Read out
Log Book via
MLog Analyser
and possibly
delete it
3 seconds
flashing
off
recording in
progress
no alarm in Log book
3 seconds
flashing
5 seconds
flashing
recording in
progress
minimum one alarm
in Log book
Check Log
Book via MLog
or Analyser
Event
Event LED EVENT/ALARM (red)
Device analyses shock event
1x flashing