PAGE 36 —DCA-150SSKII— PARTS AND OPERATION MANUAL — REV. #2 (05/08/01)
240/12
0V Hard Wire Hookup
The output terminal panel, when suppling single phase 120
volts, will provide three legs available with 333.3 amps each
on three different circuits. (See Figure 21 below.) The voltage
selector switch must be set at the single phase 240/120V
position. (See figure 20 below.)
The output terminal panel, when suppling single phase 240
volts, will provide one leg only with 166.7 amps available.
(See Figure 21 below.) The voltage selector switch must be
set at the single phase 240/120V position. (See figure 20
below.)
480/240V Hard Wire Hookup
The output terminal panel, when suppling three phase 240
volts, will provide one circuit available at 361 amps with any
two wires plus the ground. (See Figure 23 below.) The voltage
selector switch must be set at the three phase 480/277V
position. (See figure 22 below.)
The output terminal panel, when suppling 3 phase 480 volts,
will provide one circuit available at 180 amps available with
all three wires plus ground. (See Figure 23 below.) The
voltage selector switch must be set at the three phase 480/
277V position. (See figure 22 below.)
FIGURE 20. Voltage Selector Switch 240/120V Single Phase
Position
FIGURE 22. Voltage Selector Switch 480/277V Three Phase
Position
FIGURE 21. Hard Wire Hook-up at 240/120V Position
FIGURE 23. Hard Wire Hook-up at 480/240V Position
DCA-150SSKII — OUTPUT TERMINAL PANEL OVERVIEW