DCA-150SSKII — PARTS AND OPERATION MANUAL— REV. #1 (05/08/01) — PAGE 47
WARNING:
Before Starting
Engine
1. Check the lubricating oil level prior to starting the engine.
Make sure the generator is level. The oil level must be
maintained between two notches on the dipstick.
2. When there is not enough lubricating oil, fill the crankcase
with high grade motor oil. Use a high quality detergent
oil classified CC or higher (See Table 12 on page 43).
3. Check the coolant level in the radiator and subtank.
Replenish with antifreeze as necessary. Always maintain
the coolant level between the FULL and LOW markings
on the coolant container. Be sure that the radiator cap is
fastened securely.
4. Check the fuel level on the fuel gauge. If fuel is low, fill
the fuel tank with clean fresh unleaded automotive diesel.
If diesel spillage occurs, completely wipe up the spilled
fuel immediately.
Before Starting
Generator and Control Panel
CAUTION:
1. Be sure to disconnect the electrical load and switch the
main, load and G.F.C.I. circuit breakers (Figure 42) to
the “OFF” position prior to starting the engine.
NEVER start the engine with the
main, GFCI or load circuit
breakers in the ON position.
The engine's exhaust contains
harmful emissions.
ALWAYS ventilate
the exhaust when operating inside
tunnels, excavations or buildings.
Direct exhaust away from nearby
Figure 42. Main, GFCI and
Load Circuit Breakers
DCA-150SSKII — GENERATOR START-UP PROCEDURE (MANUAL)
2. Once it is determined if commercial power is required,
connect the load to the UNV terminals as shown in
Figure 43. These terminals can be found on the output
terminal panel, see page 33, Figure 14. To gain access
to the output terminals lift the UNV cover. Make sure to
tighten terminal nuts securely to prevent load wires from
slipping out.
Figure 43. UNV Terminal Lugs (Load)
NEGA
TIVE
POSTIVE
BATTER
Y
3. Connect the negative battery cable (BLACK) to the
negative post on the battery (Figure 44).
Figure 44. Battery Connections