NPort IA5000A Series
Web Console Configuration
5-33
IP address changed
The user has changed the NPort IA5000A’s IP address. When the IP address changes, the NPort IA5000A will
send an e-mail with the new IP address before the NPort IA5000A reboots. If the NPort IA5000A is unable to
send an e-mail message to the mail server within 15 seconds, the NPort IA5000A will reboot anyway, and abort
the e-mail auto warning.
Password changed
The user has changed the NPort IA5000A’s password. When the password changes, the NPort IA5000A will
send an e-mail with the password changed notice before the NPort IA5000A reboots. If the the NPort IA5000A
is unable to send an e-mail message to the mail server within 15 seconds, the NPort IA5000A will reboot
anyway, and abort the e-mail auto warning.
Power failure
We provide two DC power inputs for redundancy. The NPort IA5000A Series supports different approaches to
warn engineers automatically, such as by email or relay output. Users can connect to “Monitor -> Relay Output”
from the web console to check what event causes the warning. The relay output will be canceled after the
power recovers, or by selecting “acknowledge event” using the web console or Telnet. When the Relay Output
is sending a warning, the Ready LED will flash red until the warning event ceases.
Ethernet link down
The NPort IA5000A Series provides system maintainers with real-time alarm messages for Ethernet link down.
Even when control engineers are out of the control room for an extended period of time, they can still be
informed of the status of devices almost instantaneously when exceptions occur. The NPort IA5000A Series
supports different methods for warning engineers automatically, such as by email, SNMP trap, and relay output.
Users can connect to “Monitor -> Relay” Output from the web console to check which Ethernet port is causing
the warning. The relay output will be canceled if the failed Ethernet link is restored, or by selecting
Acknowledge Event from the web console or Telnet. When the Relay Output is issuing a warning, the Ready LED
will flash in red until the warning event ceases.
DCD changed
The DCD (Data Carrier Detect) signal has changed, also indicating that the modem connection status has
changed. For example, a DCD change to high also means “Connected” between local modem and remote
modem. If the DCD signal changes to low, it also means that the connection line is down.
When the DCD changes, the NPort IA5000A will immediately send an e-mail, send an SNMP trap,or trigger the
relay output..
DSR changed
The DSR (Data Set Ready) signal has changed, also indicating that the data communication equipment’s power
is off. For example, a DSR change to high also means that the DCE is powered ON. If the DSR signal changes
to low, it also means that the DCE is powered off.
When the DSR changes, the NPort IA5000A will immediately send an e-mail, send an SNMP trap, or trigger the
relay output.
Mail
Setting
Factory Default
Necessity
Enable, Disable
Disable
Optional
This feature helps the administrator manage how the NPort IA5000A sends e-mail to pre-defined e-mail boxes
when the enabled events—such as Cold start, Warm start, Authentication failure, etc.—occur. To configure this
feature, click the Event Type Mail checkbox.
Trap
Setting
Factory Default
Necessity
Enable, Disable
Disable
Optional