Moxa Technologies IKS-6728A-8PoE series Hardware Installation Manual Download Page 10

 

- 10 - 

Storage 
Temp. 

-40 to 85°C (-40 to 185°F) 

Ambient 
Relative 
Humidity 

5 to 95% (non-condensing) 

Standards and Certifications 

Safety 

UL 60950-1, EN 60950-1 

EMI 

FCC Part 15 Subpart B Class A, EN 55022 Class A 

EMS 

EN 61000-4-2 (ESD) Level 3, EN 61000-4-3 (RS) Level 3, 
EN 61000-4-4 (EFT) Level 3, EN 61000-4-5 (Surge) Level 
3, EN 61000-4-6 (CS) Level 3, EN 61000-4-8, EN 
61000-4-11 
Note: For better conductive radiation immunity, STP cable 
is recommended. 

Rail Traffic 

EN 50121-4 

Shock 

IEC 60068-2-27 

Freefall   

IEC 60068-2-32 

Vibration 

IEC 60068-2-6 

Warranty 

Warranty 
Period 

5 years 

Details 

See www.moxa.com/warranty 

Rack Mounting Instructions   

1.

 

Elevated Operating Ambient:

 If installed in a closed or multi-unit 

rack assembly, the operating ambient temperature of the rack 
environment may be greater than room ambient. Therefore, 
consideration should be given to installing the equipment in an 
environment compatible with the maximum ambient temperature 
(Tma) specified by the manufacturer.   

2.

 

Reduced Air Flow:

 Installation of the equipment in a rack should 

be such that the amount of air flow required for safe operation of the 
equipment is not compromised.   

3.

 

Mechanical Loading:

 Mounting of the equipment in the rack 

should be such that a hazardous condition is not achieved due to 
uneven mechanical loading.   

4.

 

Circuit Overloading:

 Consideration should be given to the 

connection of the equipment to the supply circuit and the effect that 
overloading of the circuits might have on overcurrent protection and 
supply wiring. Appropriate consideration of equipment nameplate 
ratings should be used when addressing this concern.   

5.

 

Reliable Grounding:

 Reliable grounding of rack-mounted 

equipment should be maintained. Particular attention should be 
given to supply connections other than direct connections to the 
branch circuit (e.g. use of power strips). 

 

NOTE 

The rackmount ears can be equipped on the front or rear of Moxa 
IKS-6700A/IKS-6728-8PoE switch. 

 

Restricted Access Locations   

 

This equipment is intended to be used in Restricted 
Access Locations, such as a computer room, with 
access limited to SERVICE PERSONAL or USERS 

Summary of Contents for IKS-6728A-8PoE series

Page 1: ...2014 Moxa Inc All rights reserved P N 1802067000010 IKS 6700A and IKS 6728A 8PoE Series Hardware Installation Guide First Edition September 2014...

Page 2: ...and software CD Hardware installation guide CD ROM with user s manual and SNMP MIB file Moxa product warranty statement Panel Layouts 1 System status LEDs 2 Model name 3 Reset button 4 Terminal block...

Page 3: ...3 14 Grounding screw 15 Power sockets for AC power inputs or terminal blocks for DC power inputs Dimensions Unit mm inch Fast Ethernet Interface Modules IM 6700A Series...

Page 4: ...ate 48 VDC power supplies are required to provide power to all PoE ports 50 to 57 VDC is recommended for IEEE 802 3at devices For the 48 VDC models the 48 VDC power supplies provide power for switch o...

Page 5: ...elay contact of the 2 pin terminal block connector is used to detect user configured events The two wires attached to the fault contacts form an open circuit when a user configured event is triggered...

Page 6: ...described in the table below LED Color State Description System LEDs PWR1 AMBER On Power is being supplied to the main module s power input PWR1 Off Power is not being supplied to the main module s po...

Page 7: ...n When the system is importing exporting data from or to an ABC 02 USB automatic backup device the FAULT MSTR HEAD and CPLR TAIL LEDs will blink in sequence Port Status LEDs G1 to G4 1000M TP ports le...

Page 8: ...nology Standards IEEE 802 3af at for Power over Ethernet IEEE 802 3 for 10BaseT IEEE 802 3u for 100BaseT X and 100BaseFX IEEE 802 3ab for 1000BaseT X IEEE 802 3z for 1000BaseX IEEE 802 3x for Flow Con...

Page 9: ...24 T 24 VDC 0 40A IKS 6726A 2GTXSFP 48 48 T 48 VDC 0 21A IKS 6726A 2GTXSFP HV HV T 110 VAC 0 33A 230VAC 0 24A IKS 6728A 4GTXSFP 24 24 T 24VDC 0 44A IKS 6728A 4GTXSFP 48 48 T 48VDC 0 23A IKS 6728A 4GT...

Page 10: ...he manufacturer 2 Reduced Air Flow Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised 3 Mechanical Loadi...

Page 11: ...are extremely hot Before touching the equipment you must take special precautions to protect your hands and body from serious injury Technical Support Contact Information www moxa com support Moxa Ame...

Reviews: