TROUBLESHOOTING AND REPAIR
34
Refrigeration Cycle Components
A
C
B
E
F
D
PART REPLACED
DISCONNECT AT:
Compressor
A & B
Condenser
A & C
Capillary tube
D & E
Evaporator
E & F
Removal of Refrigeration Cycle Components (Refer to 5-2-2.)
B. Removal of Refrigeration Cycle Components
CAUTION:
1.
Before any refrigeration cycle component can be replaced, it is necessary to recover the refriger-
ant using standard recovery procedures and equipment.
2.
To prevent oxidation, dry nitrogen should be conducted (flow rate 1 liters/min) through the pinch-
off tube during any brazing operation.
3.
During any component replacement involving brazing, shield nearby parts with a steel plate,
asbestos, etc., to protect them from the flame.
(1) Evaporator
(2) Capillary tube
(3) Condenser
(4) Compressor
NOTE: Hold the compressor body, not the tube, when carrying the compressor.