TROUBLESHOOTING AND REPAIR
39
B. Removal of Gauge Manifold
(1) Crimp the pinch-off tube with a pinch-off
tool.
(2) Remove the gauge manifold and the
process tube fitting. Crush the end of the
pinch-off tube.
(3) Braze the end of the pinch-off tube.
(4) Ensure that a gas leak is not present at
the pinched off portion and the brazed
end.
Reassemble the unit in the reverse order of removal.
Described below are the parts that require special
care in reassembling the unit. Perform all wiring or
rewiring as referenced in the wiring diagram.
22. Compressor Mounting
Mount the compressor on the frame, using
cushions, steel collars, spring washers, plate
washers and nuts.
23. Blower Assembly
Install blower fans (for evaporator and con-
denser).
Tightening torque:
10.84 ± 2.17 lbf•ft (150 ± 30 kgf•cm)
NOTE: After reassembling, the gap between blower
fan and housing should be 0.06 inches (1.5 mm) or
more.
24. Wiring Notice
Secure the wires using clamps so that they do
not come into contact with the edges of the
structure, etc. Secure the wires using clamps in
the same position they were before removal.
25. Perform the inspection of cooling capacity
and check for abnormal noise or abnormal
vibration.
Compressor Mounting
Blower Assembly Mounting
Removal of Gauge Manifold