[25]
User Guidelines
– TCU-200
12-06-2019
Vers. 003
ST-1
Cooling proportional value. Self-adjusting.
Do not change without consulting the manufacturer.
It is no unit of measure (proportional value that multiplies the time the cooling
solenoid valve is connected. This time is given by the PID).
Cooling Brake. Do not change without consulting the manufacturer.
Cooling gives 100% to the working temperature plus "CL.br" value. When it
comes down to this value, start the PID control.
Cooling ramp. Do not change without consulting the manufacturer.
This parameter is activated when entering the PID control.
In cycles of 8 seconds, if the temperature has not exceeded this value, it will
activate again cooling. If on the contrary it has exceeded, cooling is not activated
until the next cycle, which will return him to look.
ST-2
Type of thermocouple. Do not change without consulting the manufacturer.
We choose if the thermocouple is J type (TC 1) or Pt1000 (Pt1).
Flow meter activation.
Activate or not the flowmeter. On-OFF.
Flowmeter signal. Do not change without consulting the manufacturer.
Flow meter signal is done by 4...20mA (SrC.A) or 0..10Vdc (SrC.u).
Activation return sensor.
Activate or not in the display the return / external thermocouple
On-OFF.
Type of return / external thermocouple
We choose if the thermocouple is J type (TC 1) or Pt1000 (Pt1).
Summary of Contents for TCU-200
Page 10: ... 10 User Guidelines TCU 200 12 06 2019 Vers 003 3 2 Rear view ...
Page 38: ... 38 User Guidelines TCU 200 12 06 2019 Vers 003 17 Electrical diagram ...
Page 39: ... 39 User Guidelines TCU 200 12 06 2019 Vers 003 18 Water Circuit Diagram ...
Page 40: ... 40 User Guidelines TCU 200 12 06 2019 Vers 003 19 Control Circuit diagram ...
Page 41: ... 41 User Guidelines TCU 200 12 06 2019 Vers 003 20 Components and spare part list ...