CSD Series
Variable Frequency AC Drive
MOTORTRONICS
- 7 -
1 - 12 KHz
0.1 - 400 Hz
Digital: 0.01%
Analog: 0.4%
0.01 HZ with computer of PLC control, 0.1 Hz with keypad control with frequency
above 100 Hz
0 - 5, 0 - 10V, 4 - 20mA, 10K Potentiometer
Optional card: Bi-polar ± 5 or ±10 Vdc command available. (Specify bi-polar
command signal range)
Programmable between 30% - 200%
2 separate programmable ACCEL/DECEL times
0.1 - 3600 SEC with 2 S-curves
Programmable DECEL or free run to stop
150% for up to 1 minute
Braking Torque
200V & 400V
Class
Standard braking torque = 20%
100% braking torque available with addition of optional resistors (plus braking
transistors on units rated 15HP and above)
18 patterns, one curve programmable
IGBT transistors in a sine-coded PWM (Pulse Width Modulated) firing scheme
Approximately 200% of unit rated current
150% for 1 minute
Programmable electronic thermal overload relay
200V Class: DC bus exceeds 427V
400V Class: DC bus exceeds 854V
200V Class: DC bus voltage drop < 200V
400V Class: DC bus voltage drop < 400V
Programmable 0~2 seconds: unit can be restarted via speed search
Motor coast to stop at blown fuse
Protected by thermister/thermostat
Via charge LED
Start -up
Standard on all units
Running
Standard on all units
Operation Signal Forward/Reverse operation; individual command
Multifunction
Input Selection
Standard: 3 dry contact inputs only
Optional: 120 Vac interface card
Multifunction
Output
1 output 35Vdc, 50mA maximum
Fault Output
250 Vac 1A, 30 Vdc 1A maximum
Frequency reference bias/gain, upper lower limit, auto/manual torque boos, frequency
meter gain calibration, auto reset attempt, skip frequency, S-curve: ACCEL/DECEL,
current limit, carrier frequency adjust (1 - 12 KHz), communication link function,
energy saver, vibration control, 7 process timers
Frequency command, output frequency, output current, output voltage, P-N bus
voltage, rotation direction, engineering units
Analog output (0-10V), possible to select output frequency, setting frequency, output
voltage and P-N bus voltage
NEMA 1 (IP20) standard, NEMA 4 /4X also available (up to 10HP)
Indoor (protected from gas and dust) 3,300 feet (without derating). Use in an
enclosure with filtered forced ventilation, or if standalone, in a clean pollution-free
environment
Enclosed: -10º C to 40º C (14º F to 104º F)
Chassis: -10º C to 50º C (14º F to 122º F)
-10º C to 50º C (14º F to 122º F)
0 - 95% non-condensing
0.5G
EMC 89/336/EEC
Ap
pr
o
v
a
ls
UL listed and Canadian UL (cUL) listed, CE Approved
EMC
E
n
vi
ro
n
m
en
ta
l
C
o
ndi
ti
o
n
s
Instantaneous Overcurrent
Overload Capacity of Drive
Output
Signal
Enclosure
Humidity
Digital Operator Monitor
Built-in Functions
DC Bus Protection
Power Charge Indication
Vibration
Output Power Circuit
V/f Pattern
Overvoltage
Storage Temperature
Input
Signal
Analog Output Monitor
Location and Altitude
Ambient Temperature
Momentary Power Loss
Op
e
ra
tio
n
C
o
n
d
itio
n
s
Frequency Control Range
Frequency Accuracy
Frequency Resolution
Motor Overload Protection
Frequency Setting Signal
ACCEL/DECEL Time
Undervoltage
Heat Sink Fin Overheat
Ground Fault
Protection
Co
nt
ro
l Char
a
c
ter
is
ti
c
s
P
rot
e
c
ti
on
Fun
c
ti
ons
Carrier Frequency
Stall Prevention
Starting Torque
Summary of Contents for CSD Series
Page 2: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 74 ...
Page 4: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 76 ...
Page 30: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 26 ...
Page 32: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 28 ...
Page 65: ...CSD Series Variable Frequency AC Drive MOTORTRONICS 61 ...