Appendix D: ACE3600 Maximum Power Ratings
D-3
Module Name
Self Power
Consumption
(no active I/O)
(Watts)
Maximum
Power
Consumption
per Active I/O
(Watts)
Self Power
Consumption
(no active I/O)
Watts
Maximum
Power
Consumption
per Active I/O
Watts
Maximum
Power
Consumption
all I/Os,
LEDs Active
Watts
AC: 100 to 240 VAC
DC: 18 to 72 VDC
Vin = +13.8 VDC
Digital Input
120/230V
0.100
0.015
0.080 (5.8 mA)
0.012 (1 mA)
0.524 (38 mA)
(x16 inputs
ON)
Digital Output
ML Relay
(x8/x16)
0.120
0.010
0.100
(7.2 mA)
0.008
(0.5 mA)
0.483 (35 mA)
(x16 relays
ON)
Digital Output
EE Relay
(x8/x16)
0.170
0.200
0.136 (10 mA)
0.160
(11.6 mA)
3.26 (236 mA)
(x16 relays
ON)
Digital Output
SBO EE Relay
2 Form A (x8)
0.170
0.400
0.136 (10 mA)
0.320
(23.2 mA)
0.57 (41 mA)
Digital Output
ML Relay
120/230V
0.200
0.006
0.160
(11.6 mA)
0.005 (0.4 mA)
0.248
(18.0 mA)
(x12 relays
ON)
Digital Output
EE Relay
120/230V
0.290
0.260
0.232 (17 mA)
0.210
(0.15 mA)
3.12 (226 mA)
(x12 relays
ON)
FET Digital
Output/Digital
Input
0.120
DI = 0.014
(per input
channel)
DO = 0.014
(per output
channel)
0.100
(7.2 mA)
DI = 0.011
(per input
channel)
DO = 0.011
(per output
channel)
0.552 (40 mA)
(x32 LEDs/
inputs ON)
Mixed I/O
(DO ML +DI
IEC Type 2)
0.480
DI = 0.250
(powered by
internal 24V
PS)
DO = 0.010
0.384 (28 mA)
DI = 0.250
(powered by
internal 24V
PS)
DO = 0.008
4.70 (341 mA)
(x4 relays ON
x16 inputs ON
x4 AI ON
powered by
internal 24V
PS)
Summary of Contents for ACE3600 RTU
Page 45: ...Installation 2 25 ...
Page 46: ...Installation 2 26 Figure 2 28 19 Frame Metal Back Installation Combinations ...
Page 100: ...Digital Input Module 6 7 Module Block Diagram 16 DI ...
Page 101: ...Digital Input Module 6 8 32 DI ...
Page 120: ...Digital Output Digital Input FET Module 8 6 Module Block Diagram 16 DO DI FET ...
Page 121: ...Digital Output Digital Input FET Module 8 7 32 DO DI FET ...
Page 125: ...Digital Output Digital Input FET Module 8 11 Specifications subject to change without notice ...
Page 133: ...Digital Output Relay Module 9 8 Module Block Diagram 8 DO ...
Page 134: ...Digital Output Relay Module 9 9 16 DO ...
Page 155: ...Digital Output SBO Relay Module 11 9 Module Block Diagram 8 DO ...
Page 156: ...Digital Output SBO Relay Module 11 10 16 DO ...
Page 166: ...Analog Input Module 12 8 Module Block Diagram 8 AI ...
Page 167: ...Analog Input Module 12 9 16 AI ...
Page 178: ...Analog Output Module 13 8 Module Block Diagram 4 AO ...
Page 186: ...Mixed I O Module 14 5 Module Block Diagram Mixed I O ...
Page 193: ...Mixed Analog Module 15 4 Module Block Diagram Mixed Analog ...
Page 342: ...OPTIMIZATION General No optimization is required for the ACE3600 units 25 1 ...
Page 354: ...Break Fix Procedures Figure 29 3 Electrical Interconnection RTUs with I O slots 29 7 ...
Page 355: ...Break Fix Procedures 29 8 Figure 29 4 Electrical Interconnection RTUs with no I O slots ...