Mixed I/O Module
14-7
Mixed I/O Module Specifications
Total Number of Inputs /
Outputs
16 Digital 4 EE Relay O 4 Analog Inputs
( ±20 mA)
16 Digital 4 ML Relay O 4 Analog Inputs
( ±20 mA)
I/O Arrangement
1 group of 16 DIs with shared common
4 relay outputs - Form C
4 isolated analog inputs
DI Counter Inputs
The first 12 inputs can be configured as fast counters.
DI Frequency
0 - 1 KHz
DI Fast Counter Frequency
0 - 5 KHz, minimum pulse width 100 µS
DI Max. DC Voltage
Max. 40 V DC
DI “ON” DC Voltage Range
+11 to +30 V DC, -30 to -11 V DC
DI “OFF” DC Voltage Range
-5 to +5 V DC
DI Current
6-10 mA
Fast Capture Resolution
1 mS (Interrupt upon change of state)
Event Time Tagging
Resolution
1 mS (Interrupt upon change of state)
DI Filtering
0 to 50.8 mS (DC, programmable in 0.2 mSec steps)
DI Counter Filtering
0 to 12.75 mS (programmable in 0.05 mSec steps for inputs configured as
high speed counters)
DO Contact Voltage Ratings
Max. 60 V DC or 30 V AC RMS (42.4 V peak).
DO Contact Power Ratings
2A @ 30 V DC, 0.6A @ 60V DC or 0.6A @ 30V AC
(resistive load)
DO Relay Back Indication
Contact position - hardware back indication
DO Fail State
Configurable relay state on CPU fail: On, Off or ‘last value’
AI Resolution
16 Bit (including sign)
AI Accuracy
±0.05% of full scale @ 25ºC
AI Sampling Time
10 mSec @ 50 Hz filtering
8.33 mSec @ 60 Hz filtering
AI Smoothing
Selectable input averaging: 1, 2, 4, 8, 16, 32, 64 or 128 samples
(x10 mS)
AI max. Potential between
AIs
75 V DC, 60 V AC (RMS)
AI Impedance
Rin < 250 Ω
Summary of Contents for ACE3600 RTU
Page 45: ...Installation 2 25 ...
Page 46: ...Installation 2 26 Figure 2 28 19 Frame Metal Back Installation Combinations ...
Page 100: ...Digital Input Module 6 7 Module Block Diagram 16 DI ...
Page 101: ...Digital Input Module 6 8 32 DI ...
Page 120: ...Digital Output Digital Input FET Module 8 6 Module Block Diagram 16 DO DI FET ...
Page 121: ...Digital Output Digital Input FET Module 8 7 32 DO DI FET ...
Page 125: ...Digital Output Digital Input FET Module 8 11 Specifications subject to change without notice ...
Page 133: ...Digital Output Relay Module 9 8 Module Block Diagram 8 DO ...
Page 134: ...Digital Output Relay Module 9 9 16 DO ...
Page 155: ...Digital Output SBO Relay Module 11 9 Module Block Diagram 8 DO ...
Page 156: ...Digital Output SBO Relay Module 11 10 16 DO ...
Page 166: ...Analog Input Module 12 8 Module Block Diagram 8 AI ...
Page 167: ...Analog Input Module 12 9 16 AI ...
Page 178: ...Analog Output Module 13 8 Module Block Diagram 4 AO ...
Page 186: ...Mixed I O Module 14 5 Module Block Diagram Mixed I O ...
Page 193: ...Mixed Analog Module 15 4 Module Block Diagram Mixed Analog ...
Page 342: ...OPTIMIZATION General No optimization is required for the ACE3600 units 25 1 ...
Page 354: ...Break Fix Procedures Figure 29 3 Electrical Interconnection RTUs with I O slots 29 7 ...
Page 355: ...Break Fix Procedures 29 8 Figure 29 4 Electrical Interconnection RTUs with no I O slots ...