Expansion Module
Setting the Frame Number
The expansion module shipped from the factory is set by default to 1. If more than one I/O
expansion frame is added, this frame number (also known as frame ID) must be changed.
Procedure 17-1 describes how to set the expansion frame number using the rotary selector
switch on the front panel of the expansion module. The frame number should be changed
before powering up the module.
Procedure 17-1 How to Set the I/O Expansion Frame Number
1)
Make sure that the expansion module is not connected to a power source.
2)
Insert a small flat screwdriver into the groove on the rotary frame number selector. See
Figure 17-3.
3)
Using the screwdriver, turn the dial until the arrow points to the desired frame number.
Note: The selected frame number must not already be assigned to another expansion
module and must be in the range of 1-13 (1-9, A, B, C, D hexadecimal.)
4)
Connect the expansion module to a power source.
5)
When the expansion module is powered up, verify the selected frame number via the four
binary Expansion Address (EXP ADDR) LEDs on the front panel. This is the frame
number that will be used when communicating with the main CPU.
1
2
5
3
B
9
8
6
C
A
7
4
D
Groove
X1
X2
X4
X8
EXP
ADDR
Figure 17-3 Expansion Module Rotary Frame Number Selector Switch and
Expansion Address LEDs
The rotary frame number selector switch should not be changed while the expansion
module is running. If the switch is changed while the expansion module is running,
17-8
Summary of Contents for ACE3600 RTU
Page 45: ...Installation 2 25 ...
Page 46: ...Installation 2 26 Figure 2 28 19 Frame Metal Back Installation Combinations ...
Page 100: ...Digital Input Module 6 7 Module Block Diagram 16 DI ...
Page 101: ...Digital Input Module 6 8 32 DI ...
Page 120: ...Digital Output Digital Input FET Module 8 6 Module Block Diagram 16 DO DI FET ...
Page 121: ...Digital Output Digital Input FET Module 8 7 32 DO DI FET ...
Page 125: ...Digital Output Digital Input FET Module 8 11 Specifications subject to change without notice ...
Page 133: ...Digital Output Relay Module 9 8 Module Block Diagram 8 DO ...
Page 134: ...Digital Output Relay Module 9 9 16 DO ...
Page 155: ...Digital Output SBO Relay Module 11 9 Module Block Diagram 8 DO ...
Page 156: ...Digital Output SBO Relay Module 11 10 16 DO ...
Page 166: ...Analog Input Module 12 8 Module Block Diagram 8 AI ...
Page 167: ...Analog Input Module 12 9 16 AI ...
Page 178: ...Analog Output Module 13 8 Module Block Diagram 4 AO ...
Page 186: ...Mixed I O Module 14 5 Module Block Diagram Mixed I O ...
Page 193: ...Mixed Analog Module 15 4 Module Block Diagram Mixed Analog ...
Page 342: ...OPTIMIZATION General No optimization is required for the ACE3600 units 25 1 ...
Page 354: ...Break Fix Procedures Figure 29 3 Electrical Interconnection RTUs with I O slots 29 7 ...
Page 355: ...Break Fix Procedures 29 8 Figure 29 4 Electrical Interconnection RTUs with no I O slots ...