1.4 Positioning the stove/distance requirements
Installation in the Morsø modular system
The insert stove, Morsø 5660M, is intended for installation in the Morsø insert modular
system.
The modular system comprises 3 module types:
• Module for Morsø 5660M insert
• Module for mounting under the insert
• Side modules
Adjacent materials must be non-flammable.
When put up on brickwork, a single layer of wallpaper will, in general, be considered to be
non-flammable material. A non-flammable cover plate should cover a floor area of minimum
300 mm in front of the furnace door and 150 mm to each side in front of the stoke hole.
Please note that the floor must be of sufficient load capacity for the installation. If Morsø
5660M is intended for wall-hanging, it should likewise be verified whether the wall can take
the load of the installation.
Requirements as to distance will only be relevant in case the stove is to be installed adjacent
to flammable material.
The distance requirements are as follows:
Distance
to
furniture 1300
mm
Distance to flammable sidewall, at a right angle to the stove
400* mm
Height above flammable flooring, a minimum of
300** mm
B
B
SECTION
B-B
SCALE
1 : 12
3
2
1
C
C
SECTION
C-C
SCALE
1 : 12
1
2
3
300**
150
300
400*
Zone: Rev.:
Description
Date
Sign.:
Revisions
Title:
Drawing no.:
1:50
Til vejledning
Morsø 5660M
RSV
04.12.2017
A2
Date of print: 02-03-2018
U:\udv\Tegninger\5600\5600 Assembly.SLDASM
5600-184 a
Itemno.:
This drawing is Morsø Jernstøberi A/S' property and must not be sold, lended or copied without any written authorization from the company.
Material:
Weight kg.:
Model no.
Drawingtype:
Location of file:
Scale:
Format:
Released:
Construction: