ELECTRA
C
OMFORT
22
½ max. output
according to parameter P35
max. boiler output
according to parameter P35
Parameter
marking
Information/value
displayed in English
Importance
Setting value
Factory
setting
Autorization
Min.
verion of
the boiler
-
HW setting
Setting of heating water tempeature, going to
"summer" opeation mode under 30 °C (symbol of
summer = tap)
30 to 80, step 1
60
User
1
-
DHW setting
Setting of sanitary (domestic hot water) tempeature,
going to switch off mode under 30°C ("-" is lihtening
on the display instead of temperature value)
30 to 65, step 1
50
User
2
-
Room setting
Setting of temperature requested in refference room
under 5°C, termination regulation on basis of
temperature in refference room ("-" is lihtening on the
display instead of temperature value)
5 to 35, step 1
Ooff
User
1+A2
P1
Language
Language
CZ, EN,FR,SK,DE
EN
User
1
P2
Backlighting
Permanent backlightening of display
YES, NO
Yes
User
1
P3
Pump runout set
Pump running out
Time, temperature
Temperature
User
1
P4
Time pump runout
Time of pump running out
1 to 30, step 1 min
10
User
1
P5
Temperature pump
runout
Temperature of pump running out
25 to 70,step 1°C
40
User
1
P6
Floor temp. limit
Underfloor heating - temperature limitation
No, 20 to 55, step 1°C
No
User
1
P7
Antifrost
Antifrost protection
YES, NO
Yes
User
1
P8
Equitermic curves
Selection of equitermic curve
No, 1 to 10, step 1
No
User
1+A1
P9
Equitermic curve - start Moving of start point of equitermic curve
20 to 30 °C, step 1 °C
20
User
1+A1
P10
Tempering
Tempering - outside temperature
No, 0 to 10, step 1°C
No
User
1+A1
P11
Soft start temp.
Temperature setting delay with soft start
No, 30 to 80, step 1 °C
40
User
1
P12
Soft start time
Time settling delay
1 to 60, step 1 min
1
User
1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
P18
P-constant
Regulation constant P
0 to 99, step 1%
50
Producer
1
P19
I-constant
Regulation constant I
0 to 99, step 1%
50
Producer
1
P20
HW hysteresis
Hysteresis of heating water temperature
1 to 10, step 1°C
5
Service
1
P21
DHW hysteresis
Hysteresis of TUV/sanitary water temperature
1 to 10, step 1°C
5
Service
1
P22
High T - max P HW
Maximal output for heating systém with HT
0 to 22,5 step 2,5 kW
0
Service
1
P23
High T - max P DHW
Maximal output for storage water tank heating with HT
0 to 22,5 step 2,5 kW
0
Service
1
P24
Low T - max P HW
Maximal output for heating system with HDO (mass
remote control)
0 to 22,5 step 2,5 kW
22,5
Service
1
P25
Low T - max P DHW
Maximal output for storage water tank heating with
HDO (mass remote control)
0 to 22,5 step 2,5 kW
22,5
Service
1
P26
EIC 1
External lightening of boiler input 1 - lightening of input
0 to 12,5, step 2,5 kW
0
Service
1
P27
EIC 2
External lightening of boiler input 2
0 až 12,5, krok 2,5 kW
0
Service
1
P28
Manual low T
Manual HDO (mass remote control)switching on , after
10 min. going back NO
HDO?(mass remote control), O.K.
HDO?
Servis
1
P29
PIN
PIN
number in a format of 4 place
1234
User
3
P30
User 1
User 1
phone number according to country
-------------
User
3
P31
User 2
User 2
phone number according to country
-------------
User
3
P32
User 3
User 3
phone number according to country
-------------
User
3
P33
Errors - memory
Errors/breakdowns memory
-
Service
1
P34
Errors - memory erase
Errors/breakdowns memory deletion
O.K.
-
Service
1
P35
1 ROD POWER OUTPUT
1 heating rod power output setting
1 kW to 4 kW, step 0.1
2,5
Producer
1
Version of boiler
Version of boiler 1 = basic (control unit + relays mode)
Version of boiler 2 = TUV/sanitary water = (control unit + relays mode + TUV mode)
Version of boiler 3 = GSM = (control unit + relays mode + GSM mode)
Version of boiler 4 = Full = (control unit + relays mode + TUV mode + GSM mode)
Accessories
A1 - Outside sensor (Order No.: 4841815)
A2 - Reference room sensor ( Order No.: 4050485)
TUV set/mode (Domestic hot water/sanitary water) - Order No.: 9566.2000
GSM mode/set - Order No.: 9566.2010