background image

HIM

14

The Interface Solution Experts

Smart HART

 Loop

Interface and Monitor

Alarms Parameters

The Alarms tab controls the programmable alarm
trip(s) option. This screen will be grayed out if the
attached HIM is not equipped with at least one alarm
trip.  To program the Alarm parameters, change the
settings in the 

Alarm1 and/or Alarm2  box, then press

Quick Set. The sections of the screen are described
below.

Trip/Fault Alarms

Trip Alarm monitors a selected variable and trips

either when the variable exceeds a set value (Trip
High) or when the variable falls below a selected value
(Trip Low).  The 

Source specifies which variable will be

monitored, while the 

Trip Point sets the point at which

the alarm will trip.  After the alarm trips, the 

Dead

Band determines how far past the trip point the
variable will have to go before the alarm condition
returns to normal.

There are two types of Fault Alarms. A 

HIM Fault

Alarm monitors the health of the HART monitor. It will
trip whenever the internal error status word is set. For
example, if the HIM’s configuration file becomes
corrupt, this alarm will trip and the monitor will display
BAD_CONFIG.

  

Field Device Fault Alarm monitors

the health of the HART transmitter. This fault alarm
will trip for any of these eight malfunctions:

Figure 10.

  Alarms Tab

Device Malfunction (Bit 7)

Relay trips whenever it detects that a hardware error or
failure has occurred in the connected HART device.

Configuration Changed (Bit 6)

Relay trips whenever it detects that the connected
HART device has had its configuration changed.

Cold Start (Bit 5)

Relay trips whenever the power to the HART device is
interrupted.  It will also trip during a HART Master
Reset or Self Test Command.

Additional Status (Bit 4)

Relay trips whenever the connected HART device
reports a condition requiring HART Command #48,
which is Read Additional Information.  This indicates
that the instrument needs attention from a device with
full HART command capability.

Output Current Fixed

 

(Bit 3)

Relay trips whenever the HIM detects that the
connected HART device’s output is no longer
responding to changes in its input, and is being held at
a predefined level.

PV Analog Output Saturated (Bit 2)

Relay trips whenever it detects that both its analog and
digital representations of the Primary Variable are
outside rated operating limits, and no longer reflect the
true sensor input.

Non-PV Out of Limits (Bit 1)

Relay trips whenever one of the HART ancillary
variables (second, third or fourth), is operating outside
the limits that can be effectively measured.

PV Out of Limits (Bit 0)

Relay trips whenever the HART Primary Variable is
operating outside the limits that can be effectively
measured.

Delay & Fail Safe

By entering a value in the 

Delay box, you can specify

how long (in seconds) the alarm condition needs to
exist before the alarm trips.  

Failsafe alarms (box

checked) de-energize when in alarm condition;
Non-Failsafe alarms energize when tripped.

Summary of Contents for Smart HIM HART

Page 1: ...HIM HIMNovember 2005 224 778 00C Smart HART Loop Interface and Monitor Smart HART Loop Interface and Monitor...

Page 2: ...ions 5 Configuring the HIM 6 Installing the HIM 7 Installing the HIM into the Loop 7 Bench Checking the HIM 9 PC Configuration Software 10 HART Parameters 11 Display Parameters 13 Alarms Parameters 14...

Page 3: ...hey have to offer Works with every Smart HART Device The instrument can be programmed in minutes to inter face with every HART compatible monitoring and con trol device About this Manual Wherever you...

Page 4: ...interface over RS485 parameters as specified in U S Standard EIA RS485 Address Range Configurable from 1 to 247 Unit will assume a MODBUS address of 01 by default Baud Rate Interface supports the fol...

Page 5: ...2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12 TX TX TX TX IN IN IN IN IN IN IN IN No Label I Source AO2 I Source AO2 A MODBUS 2 A MODBUS 2 ALARM RELAYS POWER NO1 CM1 NC1 I Source or I Sink AO2 I Source or I Sink...

Page 6: ...re Once these software settings are made they are downloaded to the monitor in the form of a Configuration File and stored in the unit s non volatile memory You can choose to save a backup copy of the...

Page 7: ...or 35mm Top Hat EN50022 DIN rails ElectricalConnections After mounting you are ready to connect the HIM to the loop Each unit comes equipped with a transmitter excitation terminal which allows it to s...

Page 8: ...sted pair technique Shields are to be connected to an earth or safety ground at the unit itself The maximum length of unshielded input and output signal wiring should be 2 inches Power Sourcing Parame...

Page 9: ...ut taking advantage of the Transmitter Excitation TX terminal If you need further descriptions of the terminals see Table 2 READY INPUT TRIP 2 TRIP 1 COM 0 ADDR For a HART Transmitter the resistor mus...

Page 10: ...e device was configured HIM Tag A phrase used to identify a HIM Figure 7 HIM PC Configuration Software Screen HIM Device Status Displays how the HIM is function ing giving a brief summary of any error...

Page 11: ...ny other HART device in the loop must be configured either as a HART Secondary Master 1 per loop or as a HART Slave up to 16 per loop Conversely setting the HIM to function as the Secondary HART Maste...

Page 12: ...at Address Settings Screen To convert HEX to Decimal code perform the following steps Access the Calculator feature in Microsoft Windows by opening the Start menu Next select Programs then Accessories...

Page 13: ...HIM to sequentially display two HART variables in five second increments Directly below the Toggle checkbox are two list boxes to select the variables that you would like to be displayed Notice that...

Page 14: ...ware error or failure has occurred in the connected HART device ConfigurationChanged Bit6 Relay trips whenever it detects that the connected HART device has had its configuration changed Cold Start Bi...

Page 15: ...s information returned by certain HART instruments This provides flexibility to the requirement of alarming on additional status infor mation Choosing this feature you are given the ability to specify...

Page 16: ...et the Source as SV Set the Input Range to 0 and 400 F and the Output Range to 4mA to 20mA Click Quick Set to download the new configuration file to the HIM OutputCurrentBox The Output Current Box on...

Page 17: ...il the analog output matches the minimum point 4mA for a 4 20mA output when you click the Fix Output at Low Point button After the low point is trimmed press the Fix Output at High Point button Read t...

Page 18: ...tion CustomCurve The middle section of the screen displays the custom curve table After enabling custom curve mode and setting the variable to be monitored continue by selecting the number of points f...

Page 19: ...er to measure the level of a tank in either centimeters inches or PSI Since the tank is only 300 centimeters 10 feet high the full range of the primary variable PV output from the DP transmitter is 0...

Page 20: ...r highly skilled staff of trained technicians and engineers pride themselves on their ability to provide timely accurate and practical answers to your process instrumentation questions Factory phone n...

Page 21: ...a transmission It should be set to match the baud rate of the attached controller The interface supports the following baud rates 300 600 1200 2400 4800 9600 and 19200 Parity The HART monitor supports...

Page 22: ...RIP 2 TRIP 1 COM DEG C 0 ADDR COMMON NC normally closed NO normally open 4 20mA DCS Sensor Input NO NC DC GND 24Vdc Power Source DCC R must be 250 ohms and 1100 ohms R HART Field Instrument Temperatur...

Page 23: ...currentx 100mA HIM Status Information Bit 0 hardware failure Bit 1 EEPROM fail Bit 2 EEPROM configuration checksum error Bit 3 EEPROM calibration checksum error Bit 4 EEPROM blank Bit 5 Out of range...

Page 24: ...m 2 HART Primary variable float format HART Secondary variable float format HART Third variable float format Hart Fourth variable float format Scaled Primary variable float format Scaled Secondary var...

Page 25: ...Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 MSB device status LSB device error code Bit Position Description HART device no comms HART device malfunction HW fail EEPROM fail EEPROM checksum error...

Page 26: ...ance Director Moore Industries Europe General Mgr June 20 2003 Manufacturer sName MooreIndustries International Inc Manufacturer sAddress 16650SchoenbornStreet NorthHills CA91343 6196 USA Declaresthat...

Page 27: ...OR BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT...

Reviews: