www.miinet.com
Moore Industries-International, Inc.
- 32 -
User’s Manual
225-748-01L
February 2017
Programmable Current/Voltage Safety Trip Alarm
STA
HLPRG
SEC
TION 4
Configuring the Alarm(s)
The STA has one relay which is a Fault alarm and two user-configurable Trip alarms. The
Fault alarm has limited configuration with respect to input faults only. All diagnostic faults will
be latched and must be reset by cycling power to the unit. Input faults can be configured to be
latched/unlatched and can also be configured to be reset by the Manual Reset (MR) in addition to
front panel reset.
For more information about trip points, latching, etc., please reference the Alarm Terminology
section of this manual.
1. At the “CONFG ALARM” menu, press
SELECT
. Use the
UP
or
DOWN
buttons to toggle
between both trip alarms. When the desired alarm appears, press
SELECT.
2. At “ENTER TRIP”, press
SELECT
and enter your alarm trip value. Use the
UP
or
DOWN
buttons to set, adjust your trip value; press
SELECT
.
If you prefer to capture the input trip value instead of entering it, you must use the “INPUT
TRIP” menu. To do so, bypass the “ENTER TRIP” menu by using the
DOWN
button to
scroll to the menu; press
SELECT.
Ensure that the value you wish to capture is present
then press
SELECT.
3. Press
SELECT
at “ENTER DB” and enter your dead band value using the
UP
or
DOWN
buttons. Press
SELECT
once your desired setting appears.
4. Pressing
SELECT
at the “SET HI/LO” menu directs you to configure the alarm type as an
“ALARM HI” or “ALARM LO”. Use the
UP
or
DOWN
buttons to reach your selection and
press
SELECT.
ALARM LO–
You are notified if your process input drops below your trip point setting.
ALARM HI–
You are notified if your process input exceeds your trip point setting.
5. At the “SET LATCH” display, press
SELECT
and choose “LATCH ON” or “LATCH OFF”
using the
UP
or
DOWN
buttons; press
SELECT
.
Latching Alarm–
When a STA is configured with latching alarms, an alarm condition will
not “clear” (the relay will not change state) until the input returns to a non-alarm level
AND
manual reset terminals are shorted.
The manual reset terminals, labeled “MR” are located on the top row of terminals on the
STA (see Figure 3.3.).
6. At the “ENTER DELAY” display, press
SELECT.
Using the
UP
or
DOWN
buttons enter the
desired value (range is 0-120 seconds); press
SELECT
.
Delay–
When your unit is in an alarm condition, the delay is the amount of time you set
(0-120secs; 0-60secs for firmware versions 1.1.2 and earlier) to elapse before a relay
trips.
Note:
Firmware versions 1.1.2 and earlier permit 0-60 seconds time delay only. If a delay value
is entered greater than 60, the delay will not operate correctly. (The firmware revision of the unit
is displayed at power up and in the STA Device Info window of the PC Configuration Software)
.
7. If you are to program Alarm 2, use the
UP
or
DOWN
buttons to reach “CONFG ALRM2”
and repeat the steps performed from Alarm 1 using the appropriate values and settings.
8. At the “INPUT FAULT” display, press
SELECT,
this will display “LATCH YES?” to set latch
press
SELECT
or press
DOWN
button to display “LATCH NO?”, press
SELECT
here if
you want to disable latching.