Section 4 - STA Front Panel Configuration
The STA
(HLPRG) operating parameters are set using the pushbuttons found on the instrument’s
front panel or STA Configuration Software. This section describes the steps in order to configure
your STA using Front Panel pushbutton method.
Front Panel Push Button Configuration
There are three pushbuttons on the unit’s front panel;
UP
,
DOWN
and
SELECT
. Together with
the prompts displayed on the LCD, these are used to access menus, and to view and change the
settings.
Use
SELECT
as your “Enter” button, to make your selections.
Use the
UP
and
DOWN
buttons to navigate within the menus.
View Menu
Figure 4.1 gives an overview of the View menu.
Upon power-up, the STA displays a ‘SYS INIT’ message until the power up self test is complete.
In normal operation the View menu will display the variable as configured. This can be the
process variable, the analog output variable, or both being toggled (Refer to Configuring the
Options Menu for more details).
1. From the display, press
DOWN
.
2. If the -AO option is present, and the unit is NOT configured to toggle, the process variable
will be displayed. Continue pressing
DOWN
to view the Analog output zero, Analog output
full, trip point (AL1), trip point (AL2) and finally returning to display the process variable.
3. Enter Main Menu at any point by pressing
SELECT
.
Note:
If the Security is set to
No Access
entering SELECT will cause “SYS LOCK” to appear if
user attempts to enter MAIN menu.
Under fault conditions, the STA will display the error message describing the fault (see Table 6.1.
located in Section 6 - Operation and Maintenance for list of messages) which can be cleared
from the Reset Fault menu, MR (if configured) or by power cycling the unit.
Note:
For STA units with firmware versions 1.5 and earlier, the input fault alarm has no
configuration options, it is always latched and cannot be reset by Manual Reset (MR)
.