IPF

Page 12

Recommendations are:

Use flexible or semi-flexible, plastic, pneumatic
tubing and plastic fittings, if possible.

Provide clip- or bracket-type support at 30 cm
(1 ft) intervals, and provide independent support
for any components or equipment installed in the
lines.  Use cushioning brackets to dampen
vibration, if possible.

Avoid “straight-line” connections.

Provide auxiliary support for the filter/regulator (if
equipped), especially in areas where shock and
vibration are prevalent.

Do not over-tighten the fittings.  A torque of 10 to
15 N•m (7.4 to 11.1 ft/lbs) is adequate.

Filters

.  The IPF requires filtered, dry, regulated,

instrument-quality air to prevent clogging, and to
ensure extended periods of maintenance-free
operation.  Moore Industries suggests the following
levels of filtering protection:

Pre-filter –  A general purpose “rough” filter, used
to reduce particulate matter to 5 microns in size.
Also removes bulk liquids.  Although not re-
quired, this filter is especially recommended to
protect the 0.01 micron final filter when used.

Final Filter –  A second, final filter is recom-
mended, to remove particulate matter in sizes
down to 0.01 micron.  This filter removes virtually
all condensable liquids from the air stream as
well.

Filter/Regulator Module Option –  A  combined
filter/regulator assembly, the FR1 Option, offered
as an accessory for the IPF, removes particles
down to 0.01 micron, supplying regulated,
instrument-quality air to the unit.  This space-
saving module is affixed to the IPF supply port,
and comes with a pressure gauge scaled in both
psi (0-60) and bars (0-4).

Operation

Once its calibration has been checked or adjusted,
and the unit has been installed properly, the IPF
operates unattended.  It requires only a minor
periodic maintenance procedure, detailed in the next
section of this manual.

Remember that if an IPF is installed in an open loop,
it may appear to drift over extended periods of time,
due to the lack of corrective feedback.

If the unit is determined to be the cause of a loop
irregularity, carry out the maintenance procedure in
the next section of this manual.  If problems persist,
refer to the Troubleshooting Section.

Instrument-quality Air.  

Air from the application

continuously flows through the IPF during operation.
Depending upon the purity of the air supply, the
unit’s internal assembly may have to be removed
and cleaned at comparatively short intervals to
ensure continued optimum performance.

Initially, random checks can help establish a satisfac-
tory maintenance interval geared to the user’s air
supply cleanliness.  Refer to the next section for
instruction on the disassembly and cleaning of the
IPF.

Maintenance

Before beginning IPF maintenance, the unit must be
removed from its application.  It is strongly recom-
mended that the maintenance procedures be per-
formed in a clean, controlled environment, such as at
a technicians’ bench, in a laboratory, etc..  Several
internal parts are small and precision-machined;
easily lost or damaged if an attempt is made to
perform maintenance in the field.

After maintenance, each IPF should be recalibrated
before it is returned to service.  Refer to the Calibra-
tion Section of this manual for instructions.

Summary of Contents for IPF

Page 1: ...Field Mount Current to Pressure Transmitter May 2016 No 170 702 00 D 1992 by Moore Industries International Inc USER S MANUAL IPF...

Page 2: ...anada TOLLFREE 1 800 999 2900 UnitedKingdom FREEPHONE 0800525107 Australia TOLLFREE 008251928 16650 Schoenborn Street Sepulveda California 91343 U S A Tel 818 894 7111 Tlx 65 1322 FAX 818 891 2816 CON...

Page 3: ...eral third party industrial certifying agencies Contact your Moore Industries Sales Representative for the most current list of IPF certifications and approvals The unit has two electrical conduit dim...

Page 4: ...he combined effects of linearity hysteresis and repeatability For 3 27 psig output units or 10 50 mA input units error not to exceed 1 of span Linearity defined per SAMA standard PMC 20 1 1973 Ambient...

Page 5: ...using The example outlines the significance of each field of information in a typical IPF model number Calibration Every IPF is fully tested and calibrated at the factory prior to shipment Before inst...

Page 6: ...ore Industries but should be available in most labs or maintenance areas Calibration Setup To prepare the IPF for calibration disassemble the unit as shown in figure 1 and connect it to your calibrati...

Page 7: ...LOCK DETAIL I I N TYPE TERMINAL BLOCK DETAIL TERMINAL CONNECTIONS COVER ZERO ADJUST SCREW INTERNAL ASSEMBLY REMOVAL TAB SPAN POTENTIOMETER RUBBER RETAINING STRAP NE TYPE It is equipped with a slip clu...

Page 8: ...sing and to front panel of IPF For NE type units Route wiring through conduit opening in external sub housing terminal block assembly 5 Connect positive lead of adjustable current source to I terminal...

Page 9: ...to stabilize Calibration Procedure To perform the recommended bench check for the IPF first perform the setup as described in the preceding section The calibration procedure con sists of a basic chec...

Page 10: ...ed in an open loop this prevents compensating adjustments to the system input Mounting Figure 3 gives the IPF s outline dimensions The illustration also gives the dimensions of the available FR1 Optio...

Page 11: ...HREADS FOR WPM AND WPMP HOUSINGS FR1 OPTION APPROX 145 8 mm 5 7 in WHEN INSTALLED 9 14 mm 0 36 in DIAMETER 4 MOUNTING HOLES N TYPE TERMINAL CONNECTIONS 18 6 mm 0 72 in N TYPE 160 mm 6 28 in 94 mm 3 68...

Page 12: ...igure 4 Mounting the IPF on Vertical and Horizontal Pipe PNEUMATIC INSTRUMENT OR LOAD SUPPLY PORT OUTPUT PORT IPF CURRENT INPUT 4 20 OR 10 50 mA I I REGULATED INSTRUMENT AIR SUPPLY Figure 5 IPF Instal...

Page 13: ...to the 1 4 inch NPT female port on the side of the unit labeled SUPPLY Connect the output line to the 1 4 inch NPT female port labeled OUTPUT Refer to the unit front panel which identifies the IPF por...

Page 14: ...supply port and comes with a pressure gauge scaled in both psi 0 60 and bars 0 4 Operation Once its calibration has been checked or adjusted and the unit has been installed properly the IPF operates...

Page 15: ...must be cut to perform the maintenance cleaning Cut the wires as close to their butt connectors as possible Equipment Specifications Notes Instrument Quality Air or Nitrogen Supply Reduced to between...

Page 16: ...low out subassembly Put small amount of alcohol in air passage and set subassembly aside Cleaning the Pneumatic Block Refer to figure 7 to disassemble the IPF pneumatic block and when performing the f...

Page 17: ...13 Clean orifices and surfaces on section as before SECTION 1 HOLE ROLL IS UP ROLL IS DOWN HOLE RESTRICTOR HOLE SUPPLY SCREEN PNEUMATIC BLOCK FLAPPER NOZZLE MECHANICAL SUB ASSEMBLY Figure 7 IPF Intern...

Page 18: ...ned using an AWG 24 20 butt connector and heat shrink tubing available from Moore Industries Use of non specified connectors invalidates the group N certification Check to make sure that the spring is...

Page 19: ...the instructions found on the back cover of this manual If a problem is suspected with the IPF review the following steps 1 Verify that bench instruments used to take measurements have the proper rang...

Page 20: ...just ahead of each pressure regulator Water The amount of water in an air system depends on temperature pressure and the relative humidity of the air The amount of contamination therefore tends to var...

Page 21: ...IN OR MULTIPLE ON BRANCH LINES All Filters should have automatic drains and service indicators to show when elements need changing NOTE MAIN LINE TO OTHER BRANCHES PRESSURE REGULATOR PURIFIED AIR TO I...

Page 22: ...filtration to prevent oil contamination of the desiccant as well as to prevent desiccant fines from introducing new contamination ISA Specifications The Instrument Society of America standard ISA S73...

Page 23: ...R BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT B...