background image

IPF

Page 17

To re-connect current wiring in N-type IPF’s,
connect the wires with the same color (black-to-
black, and red-to-red).  Use a crimping tool to
secure the connection.

6. Reseat IPF faceplate, and secure it using the

Phillips-head screws, and re-secure the top
cover of the housing.

7. Calibrate unit.  Refer to Calibration Section of

this manual.

Drain Check.  

System filters have automatic drains,

which depend on the fluctuation of system pressure
to induce drainage.  A stable system may not drain
efficiently.

Periodically check for clogs, and drain system’s
filters by pushing the drainage valve with a small
probe or wire.

Troubleshooting

Many components of the IPF have been thermally
aged, tested, and selected using a computer-aided
design program.  This usually makes field repair
unnecessary.

It is therefore recommended that any properly
maintained unit found to be performing below
specifications be returned to the factory in accor-
dance with the instructions found on the back cover
of this manual.

If a problem is suspected with the IPF, review the
following steps:

1. Verify that bench instruments used to take

measurements have the proper range and
accuracy and are within current certification
period limits.

2. If a change in the relationship between the input

and output is detected, attempt a re-calibration of
the IPF.

3. If the response time lengthens, or if the span

drops, this may indicate a blockage due to air
supply contamination.  Follow the instructions in
the Maintenance Section of this manual.

The Zero Adjust Screw.  

This screw has a flange to

prevent its being turned too far counterclockwise
during adjustment.  Forcing the screw past the point
at which its flange comes into contact with the unit
front panel could disengage it from the internal
assembly.

If this happens, disassemble the IPF as described in
the Maintenance Section of this manual.

Visually inspect the screw, and if serviceable, hold
down the flapper arm, and turn the screw clockwise
until its pin is in a position to hold the arm.

Refer to the Calibration Section of this manual, and
perform a unit recalibration.

Summary of Contents for IPF

Page 1: ...Field Mount Current to Pressure Transmitter May 2016 No 170 702 00 D 1992 by Moore Industries International Inc USER S MANUAL IPF...

Page 2: ...anada TOLLFREE 1 800 999 2900 UnitedKingdom FREEPHONE 0800525107 Australia TOLLFREE 008251928 16650 Schoenborn Street Sepulveda California 91343 U S A Tel 818 894 7111 Tlx 65 1322 FAX 818 891 2816 CON...

Page 3: ...eral third party industrial certifying agencies Contact your Moore Industries Sales Representative for the most current list of IPF certifications and approvals The unit has two electrical conduit dim...

Page 4: ...he combined effects of linearity hysteresis and repeatability For 3 27 psig output units or 10 50 mA input units error not to exceed 1 of span Linearity defined per SAMA standard PMC 20 1 1973 Ambient...

Page 5: ...using The example outlines the significance of each field of information in a typical IPF model number Calibration Every IPF is fully tested and calibrated at the factory prior to shipment Before inst...

Page 6: ...ore Industries but should be available in most labs or maintenance areas Calibration Setup To prepare the IPF for calibration disassemble the unit as shown in figure 1 and connect it to your calibrati...

Page 7: ...LOCK DETAIL I I N TYPE TERMINAL BLOCK DETAIL TERMINAL CONNECTIONS COVER ZERO ADJUST SCREW INTERNAL ASSEMBLY REMOVAL TAB SPAN POTENTIOMETER RUBBER RETAINING STRAP NE TYPE It is equipped with a slip clu...

Page 8: ...sing and to front panel of IPF For NE type units Route wiring through conduit opening in external sub housing terminal block assembly 5 Connect positive lead of adjustable current source to I terminal...

Page 9: ...to stabilize Calibration Procedure To perform the recommended bench check for the IPF first perform the setup as described in the preceding section The calibration procedure con sists of a basic chec...

Page 10: ...ed in an open loop this prevents compensating adjustments to the system input Mounting Figure 3 gives the IPF s outline dimensions The illustration also gives the dimensions of the available FR1 Optio...

Page 11: ...HREADS FOR WPM AND WPMP HOUSINGS FR1 OPTION APPROX 145 8 mm 5 7 in WHEN INSTALLED 9 14 mm 0 36 in DIAMETER 4 MOUNTING HOLES N TYPE TERMINAL CONNECTIONS 18 6 mm 0 72 in N TYPE 160 mm 6 28 in 94 mm 3 68...

Page 12: ...igure 4 Mounting the IPF on Vertical and Horizontal Pipe PNEUMATIC INSTRUMENT OR LOAD SUPPLY PORT OUTPUT PORT IPF CURRENT INPUT 4 20 OR 10 50 mA I I REGULATED INSTRUMENT AIR SUPPLY Figure 5 IPF Instal...

Page 13: ...to the 1 4 inch NPT female port on the side of the unit labeled SUPPLY Connect the output line to the 1 4 inch NPT female port labeled OUTPUT Refer to the unit front panel which identifies the IPF por...

Page 14: ...supply port and comes with a pressure gauge scaled in both psi 0 60 and bars 0 4 Operation Once its calibration has been checked or adjusted and the unit has been installed properly the IPF operates...

Page 15: ...must be cut to perform the maintenance cleaning Cut the wires as close to their butt connectors as possible Equipment Specifications Notes Instrument Quality Air or Nitrogen Supply Reduced to between...

Page 16: ...low out subassembly Put small amount of alcohol in air passage and set subassembly aside Cleaning the Pneumatic Block Refer to figure 7 to disassemble the IPF pneumatic block and when performing the f...

Page 17: ...13 Clean orifices and surfaces on section as before SECTION 1 HOLE ROLL IS UP ROLL IS DOWN HOLE RESTRICTOR HOLE SUPPLY SCREEN PNEUMATIC BLOCK FLAPPER NOZZLE MECHANICAL SUB ASSEMBLY Figure 7 IPF Intern...

Page 18: ...ned using an AWG 24 20 butt connector and heat shrink tubing available from Moore Industries Use of non specified connectors invalidates the group N certification Check to make sure that the spring is...

Page 19: ...the instructions found on the back cover of this manual If a problem is suspected with the IPF review the following steps 1 Verify that bench instruments used to take measurements have the proper rang...

Page 20: ...just ahead of each pressure regulator Water The amount of water in an air system depends on temperature pressure and the relative humidity of the air The amount of contamination therefore tends to var...

Page 21: ...IN OR MULTIPLE ON BRANCH LINES All Filters should have automatic drains and service indicators to show when elements need changing NOTE MAIN LINE TO OTHER BRANCHES PRESSURE REGULATOR PURIFIED AIR TO I...

Page 22: ...filtration to prevent oil contamination of the desiccant as well as to prevent desiccant fines from introducing new contamination ISA Specifications The Instrument Society of America standard ISA S73...

Page 23: ...R BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT B...

Reviews: