5. Setting up the device
Menu level
Parameterization level
Rescaling the measuring input values,
Default:
With the aid of this function, you can rescale the input value of
20 mA
without
applying a measuring signal. If sensor calibration has been selected, these
parameters are not available.
Rescaling the measuring input values,
Default:
With the aid of this function, you can rescale the input value of
4 mA
without
applying a measuring signal. If sensor calibration has been selected, these
parameters are not available.
Setting the tare/offset value,
Default:
The given value is added to the linerarized value. In this way, the characteristic
line can be shifted by the selected amount.
Zero point slowdown,
Default:
With zero point slowdown, a value range around zero can be preselected at which
the display shows zero. If, for example, a 10 is set, the display would show a zero
in the range from -10 to +10 and continue below it with -11 and above it with +11.
5.4. Extended parameterization
By pressing the
[▲]
&
[▼]
keys during standard parameterization for one second, the display
switches to the extended parameterization mode. Operation is the same as in standard
parameterization.