Page 13
XG0816 - 150204.1
H*38DF PFC Peninsula Gas Fireplace
Installation
The Venting Graph: H*38PF*
Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the fireplace flue collar to
the wall flange of the termination. Plot on the Venting Graph
Figure 12
or 13
with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 114" and the horizontal
run to the wall flange of the vent termination is 126", this would be
an acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 48" and the horizontal
run to the wall flange of the vent termination is 84",
this would
NOT be an acceptable installation�
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 60" and
the horizontal run to the wall flange of the vent termination is 144",
this would NOT be an acceptable installation�
Figure 12�
H38PF* or HL38PF* Top Vent
Venting Graph for
wall mounted
terminations.
Figure 12a�
H38PF* or HL38PF* Top Vented,
wall mounted installation with
one
90° bend.
The vent run must comply with Venting Graph for
Top vent, wall
mounted
terminations,
Figure 12.
Section 3-3-1:
VENTING LAYOUT: Wall mounted termination�
Selection of components and details of venting layout should
adhere to the following guidelines:
Vent terminations must
not
be recessed in walls or siding.
For Heat Shield requirements see
Section 3-3-3
.
Once the proposed venting layout has been determined refer
to
Figure
12, 13, 14, or 14a
to ensure the layout is acceptable.
Notes Wall Mounted Terminations:
TOP VENT
All measurements for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs
must
fall within the limits set by the venting graph,
see
Figure 12 or 13
.
Figure 13�
HP38PF* Top Vent
Venting Graph for
wall mounted
terminations.
58”
A
C
B
.
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
If your installation does not fall with-
in the venting graph parameters,
please contact a local Montigo
dealer for Power Venting options.
19”
42”
46”
A
C
B
If your installation does not fall with-
in the venting graph parameters,
please contact a local Montigo
dealer for Power Venting options.
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
Figure 13a�
HP38PF* Top Vented,
wall mounted installation with one
90° bend.
The vent run must comply with Venting Graph for
Top vent, wall mounted
terminations,
Figure 13.
Heat Shield
Termination
Exterior
Wall
Hearth
Flex or Rigid
Insulated Sleeve
CRS101
19” Max
58”Min.
Heat Shield
46”Min.
Termination
Exterior
Wall
Hearth
Flex or Rigid
Insulated Sleeve
CRS101
42” Max.