10
26D3311
26D3311
11
���
���
��
�
�
�
�
���
�
�
���
�����
��
���
�����
��
���
�����
��
��
���
���
�
CLEARANCES
AND
HEIGHT REQUIREMENTS
NOTE: Clearances are necessary to combustible
surfaces only. No clearance is necessary for
noncombustible surface.
Sidewall and ceiling clearances:
The clearance from
the inside of the appliance to any combustible adjacent wall
should no be less than 15".
See Figure 5.
Ceiling clearance:
The ceiling must be at least 42" from
the top of the firebox opening.
See Figure 5.
Back wall clearance:
The appliance must be placed at
least 3" away from a combustible back wall.
Floor clearance:
The fireplace may not be installed onto
any combustible flooring material, such as carpeting, vinyl
or tile without the hearth or a minimum 22 GA (0.030")
metal or a minimum 1/2" wooden base covering the entire
width and depth of the base.
Mantel clearances:
The canopy supplied with the unit
must be installed. If a combustible mantel is installed. It must
meet the clearance requirements shown in
Figure 8.
The dimensions shown in Figures 5 and 8 and defined in the fireplace manufacturer's
instructions are
minimum clearances
to maintain when installing this heater. Left and
right clearances are determined when facing the front of the heater.
Follow these instructions carefully to ensure safe installation. Failure to follow
instructions exactly can create a fire hazard.
W
ARNING
Figure 5 - Sidewall and Ceiling Minimum
Clearances
Figure 6 - Dimensions for Installing in
Masonry Fireplace in a UL Listed Box
BEFORE INSTALLING THE FIREPLACE INSERT
Have fireplace floor and chimney professionally cleaned to
remove ashes, soot, creosote or other obstructions. Close
and seal any fresh air vents or ash clean-out doors located
on floor or wall
Accessory Face Plates
A B
Small
33" 43"
Large
36" 50"