background image

17

CWC Series Woodburning Fireplace

87D1504

Only unvented gas log sets which have been found to comply with 
the Standard for Unvented Room Heaters, ANSI Z21.11.2, are to be 
installed in this fireplace.

If installing an unvented gas log set, refer to statement below:

Installing Line for gas Logs

MHSC fireplaces are designed to accept a 1/2" gas 
line for installation of an approved gas appliance.  
(MHSC manufactures a wide variety of gas logs for 
use in MHSC fireplaces.)
Be sure to have the appliance installed in accordance 
with building codes.  
Gas connection may enter from either left or right side 
of the fireplace.
Locate appropriate gas line access hole in the outer 
casing of fireplace and remove insulation from gas line 
tube.  (Fig. 27)
From inside the fireplace, locate the knockout on 
the firebrick -- be sure you are on the appropriate or 
"gas line" side of the fireplace.  Using a flat bladed 
screwdriver or small chisel and hammer, carefully tap 
around the knockout until it loosens and falls out.
Install 1/2" certified gas pipe through opening.  After 
gas pipe installation is complete, use insulation that 
was removed from gas line tube to repack space 
around the pipe.  Material should be inserted from out-
side of the fireplace and packed tightly to totally seal 
between the pipe and tube.

NOTe:  gas pipe should not come in contact with 
any wood structures until it has reached a point at 
least one (1) inch away from fireplace side. 
NOTe:

 When installing an ANSI Z21.11.2 ventless 

appliance, the finishing materials used for the mantel 
must be rated at 250°F or greater.
BTU input of a gas appliance installed in fireplace 
should be rated less than 100,000 BTU/Hr.
Gas pipe installation is intended for connection to a 
decorative gas appliance only when (1.) incorporat-
ing an automatic shut-off device and (2.) complying 
with the Standard for Decorative Gas Appliances for 
Installation in Vented Fireplaces (ANSI Z21.60) 

or 

CSA draft requirements for Gas-Fired Log Lighters for 
Woodburning Fireplaces (Draft No. 4, August 1993). 
Decorative gas appliance should be installed in accor-
dance with the National Fuel Gas Code, ANSI Z223.1/
NFPA 54 (latest edition).

FPC560

Fig. 27

  Gas line access.

1"

Min.

FPC560

WMC 

Gas line access

1/29/99

1/2"

Hole in Outer Casing

Fireplace Top View

Gas Line 

Tube

Ceramic 

Knockout

Supply 

Line

Repack Insula-

tion

Hole in Outer 

Casing

Ceramic Knock-

out

(Both sides)

CAUTION:  WHeN USINg DeCORATIVe gAS AP-
PLIANCe, FLUe DAMPeR MUST be SeT IN FULLY 
OPeN POSITION.  IF YOU HAVe gLASS DOORS 
ON THe FIRePLACe, THeY MUST ALSO be FULLY 
OPeNeD.
WARNINg: DO NOT OPeRATe AN UNVeNTeD gAS 
LOg SeT IN THIS FIRePLACe WITH THe CHIMNeY 
ReMOVeD.
WARNINg: WHeN INSTALLINg AN UNVeNTeD gAS 
LOg SeT, THe MHSC MODeL CAbL OR CAbR 4" 
ADJUSTAbLe HOOD MUST be USeD.

Summary of Contents for CWC400

Page 1: ...se in U S Canada Underwriter s Laboratories Report No MH7603 DO NOT DISCARD THIS MANUAL Retain for future use 87D1504 12 09 Rev 4 FP583A WMC 12 18 98 CWC Series Woodburning Fireplaces Homeowner s Inst...

Page 2: ...HSC in combination or assembly with a MHSC fire place system notwithstanding any indepen dent testing laboratory or other third party ap proval of such component parts or accessory Any such action may...

Page 3: ...203mm 3 6 9 1 4 m m Fig 2 CWC500 Series specifications and framing FP592A CWC500 Series Woodburning Fireplace Circulating Model FP590A WMC36 SPECS 1 28 99 djt B 1 6 m m Z x 13mm Z x 36 914mm 35Z v 895...

Page 4: ...Outlet Grille Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Inlet Grille Outside Air Cover Plate Electrical Access Gas Line Access both sides Nai...

Page 5: ...1 0 0 1 0 31 60 0 1 0 1 0 34 65 0 0 2 0 0 37 70 1 1 0 1 1 41 77 0 0 1 1 1 45 83 0 1 2 0 1 47 87 0 0 0 2 1 51 94 0 1 1 1 1 53 98 0 0 3 0 1 56 103 0 1 0 2 1 59 108 0 0 2 1 1 62 113 0 1 3 0 1 64 117 0 0...

Page 6: ...2 609 mm above the peak of the roof but never less than 3 914 mm in height above the highest point where it passes through the roof 2 If a horizontal distance from the chimney to the peak of the roof...

Page 7: ...u live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of fireplace with a noncomb...

Page 8: ...tions Read all instructions before beginning installation Fol low instructions carefully The SCVS speed control may be used as an alternate wall switch in lieu of the single pole Listed 1 5 Amp 120V s...

Page 9: ...bows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very important to in...

Page 10: ...FP551 WF551 BR BC 9 29 97 See Fig 12 See Fig 12 Existing Ceiling Joists Ceiling New Framing Members Chimney Hole Fig 12 Ceiling chimney hole sizes necessary for installing firestop spacer Size of Chim...

Page 11: ...y snap together Once sections are snap locked in place it is extremely difficult to get them apart Make sure the pipe is firmly snapped and locked together as each pipe section is mounted When install...

Page 12: ...framing hole Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails Attic shields are not required at the roof Continue Installing Pipe to Complete Run C...

Page 13: ...c tions all pipes should extend Installing Top Housing or Termination Follow the installation instructions provided with the chimney termination you have selected Installing Chimney In a Chase Refer t...

Page 14: ...Wall Shield Model SP40 or a specifically built wall shield described below The special wall shield design described in Figure 19 is an alternate method of adding protection to side walls and can be u...

Page 15: ...om manufacturer of the material Fac tors are related by the formula K 1 R T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R v...

Page 16: ...d material per inch material Example of Determining Hearth Extension Equivalents To determine the thickness required for any new mate rial Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in ne...

Page 17: ...en the pipe and tube Note Gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from fireplace side NOTE When installing an ANSI Z21 11 2 v...

Page 18: ...D0131 26D0131 5 Damper Knob Wood 7536177 7536177 6 Firebrick Left Side 3041104 3034102 7 Firebrick Back 3030102 3034104 8 Firebrick Right Side 3041105 3034103 9 Firebrick Hearth 3041103 3034105 10 Scr...

Page 19: ...d the coverage provided by the owner s insurance Accessories Contact your Monessen distributor or dealer for finishing Mantels available in a wide selection of styles Glass Door Optional Bi Fold door...

Page 20: ...e chimney cap used to PLTSK8 SK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 SK8 through a chase Incl...

Page 21: ...m the chimney to combustible framing With 16 center lines Attic Insulation Shield Used to prevent attic insulation from FS2100 HT 3 wall CF 11 contacting the chimney system Canada Chimney Collar Enclo...

Page 22: ...22 CWC Series Woodburning Fireplace 87D1504...

Page 23: ...re dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this fireplace to be in compliance with your local b...

Page 24: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: