background image

11

CWC Series Woodburning Fireplace

87D1504

Installing Outside Air Kit

An outside air kit is installed in all CWC Series Fire-
places. If desired, or if local codes mandate the use of 
an air kit, then an AK-MST is required to complete the 
installation (from air kit to the outdoors). If the outside 
air kit is to be used, the AK-MST 

MUST

 be installed 

beFORe

 the fireplace is enclosed. Refer to the AK-

MST instructions for field installation. The outside air 
control lever is located at the front edge of the left side 
brick. To ‘open’, push the control lever down toward 
the hearth brick. To ‘close’, pull the control lever up 
and over. (Fig. 16)

FPC558

Fig. 17 

 Install pipe, listening for the snap-lock to fasten.

UP

FPC558

WMC

Pipe install

Circulating models

1/29/99   djt

Inner Pipe Section

Pipe 

Rim

Pipe 

Rim

Hem

Lance

FP270/271

CR Series

2/19/99   djt

elbow Strap

Angled Strap

Fig. 18 

 Attach straps to a structural framing member.

FP270/271

Support Structure

Elbow Strap

(Must be tight)

Ceiling 

Hole 

Framing

Angle Firestop

Chimney Support Strap

(Must be tight)

CLOSED

OPEN

WF 710

OUTSIDE AIR LEVER

WOOD FIREPLACES

5/28/98

FP710

Fig. 16

  Outside air operation.    

 

Installing the Chimney System

Start by attaching the first chimney section to the collar 
on top of the fireplace.

  

Install the pipe as pictured in Figure 17.  When  you 
get a good lock, you will hear the pipe clearly snap 
together. Once sections are snap-locked in place, it is 
extremely difficult to get them apart.  

Make sure the 

pipe is firmly snapped and locked together as each 
pipe section is mounted.

When installing elbows, only outer pipe will snap- lock.  
Middle pipes simply slide into position.   Be sure to 
always attach straps on upper elbow to a structural 
framing member. (Fig. 18)
Continue installing the pipe as required until pipe is 
installed up through the ceiling.  At this point, you must 
install a firestop spacer.

Installing the Firestop Spacer

 in the Ceiling Hole

A firestop spacer is used to keep pipe spaced properly 
and required for safety.
Nail the firestop spacer (at each corner) to the framing 
members of the ceiling hole. 

NOTe: 

 A firestop spacer 

is not required at the roof.

Hole sizes listed in Figure 13 for angled firestop spacers 
provide minimum required air space to chimney pipe for 
ceiling thickness up to 8" (203 mm).  When combined 
thickness of ceiling material, ceiling joists and flooring 
material exceeds 8" (203 mm), adjustments must be 
made in framing to assure that minimum air spaces to 
chimney are maintained.

Proper Firestop Spacer Installation

Figure 19 shows different installation procedures for  
both an area that 

is

 an attic and  an area that 

is not

 an 

attic.
If the area above the ceiling

 is not 

an attic, position the 

firestop spacer with the flange on the ceiling side and the 
angled portion extending up into the hole.
If the area above the ceiling 

is

 an attic, position the 

firestop spacer with the flange on the top of the framed 

Summary of Contents for CWC400

Page 1: ...se in U S Canada Underwriter s Laboratories Report No MH7603 DO NOT DISCARD THIS MANUAL Retain for future use 87D1504 12 09 Rev 4 FP583A WMC 12 18 98 CWC Series Woodburning Fireplaces Homeowner s Inst...

Page 2: ...HSC in combination or assembly with a MHSC fire place system notwithstanding any indepen dent testing laboratory or other third party ap proval of such component parts or accessory Any such action may...

Page 3: ...203mm 3 6 9 1 4 m m Fig 2 CWC500 Series specifications and framing FP592A CWC500 Series Woodburning Fireplace Circulating Model FP590A WMC36 SPECS 1 28 99 djt B 1 6 m m Z x 13mm Z x 36 914mm 35Z v 895...

Page 4: ...Outlet Grille Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Inlet Grille Outside Air Cover Plate Electrical Access Gas Line Access both sides Nai...

Page 5: ...1 0 0 1 0 31 60 0 1 0 1 0 34 65 0 0 2 0 0 37 70 1 1 0 1 1 41 77 0 0 1 1 1 45 83 0 1 2 0 1 47 87 0 0 0 2 1 51 94 0 1 1 1 1 53 98 0 0 3 0 1 56 103 0 1 0 2 1 59 108 0 0 2 1 1 62 113 0 1 3 0 1 64 117 0 0...

Page 6: ...2 609 mm above the peak of the roof but never less than 3 914 mm in height above the highest point where it passes through the roof 2 If a horizontal distance from the chimney to the peak of the roof...

Page 7: ...u live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of fireplace with a noncomb...

Page 8: ...tions Read all instructions before beginning installation Fol low instructions carefully The SCVS speed control may be used as an alternate wall switch in lieu of the single pole Listed 1 5 Amp 120V s...

Page 9: ...bows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very important to in...

Page 10: ...FP551 WF551 BR BC 9 29 97 See Fig 12 See Fig 12 Existing Ceiling Joists Ceiling New Framing Members Chimney Hole Fig 12 Ceiling chimney hole sizes necessary for installing firestop spacer Size of Chim...

Page 11: ...y snap together Once sections are snap locked in place it is extremely difficult to get them apart Make sure the pipe is firmly snapped and locked together as each pipe section is mounted When install...

Page 12: ...framing hole Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails Attic shields are not required at the roof Continue Installing Pipe to Complete Run C...

Page 13: ...c tions all pipes should extend Installing Top Housing or Termination Follow the installation instructions provided with the chimney termination you have selected Installing Chimney In a Chase Refer t...

Page 14: ...Wall Shield Model SP40 or a specifically built wall shield described below The special wall shield design described in Figure 19 is an alternate method of adding protection to side walls and can be u...

Page 15: ...om manufacturer of the material Fac tors are related by the formula K 1 R T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R v...

Page 16: ...d material per inch material Example of Determining Hearth Extension Equivalents To determine the thickness required for any new mate rial Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in ne...

Page 17: ...en the pipe and tube Note Gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from fireplace side NOTE When installing an ANSI Z21 11 2 v...

Page 18: ...D0131 26D0131 5 Damper Knob Wood 7536177 7536177 6 Firebrick Left Side 3041104 3034102 7 Firebrick Back 3030102 3034104 8 Firebrick Right Side 3041105 3034103 9 Firebrick Hearth 3041103 3034105 10 Scr...

Page 19: ...d the coverage provided by the owner s insurance Accessories Contact your Monessen distributor or dealer for finishing Mantels available in a wide selection of styles Glass Door Optional Bi Fold door...

Page 20: ...e chimney cap used to PLTSK8 SK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 SK8 through a chase Incl...

Page 21: ...m the chimney to combustible framing With 16 center lines Attic Insulation Shield Used to prevent attic insulation from FS2100 HT 3 wall CF 11 contacting the chimney system Canada Chimney Collar Enclo...

Page 22: ...22 CWC Series Woodburning Fireplace 87D1504...

Page 23: ...re dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this fireplace to be in compliance with your local b...

Page 24: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: