background image

6

CWC Series Woodburning Fireplace

87D1504

Planning Information

Preplanning an installation is very important to ensure 
safety and to save time and money.  An installer must 
predetermine where a fireplace will be set and how the 
chimney system will be run.

Mounting the Fireplace

A fireplace may be mounted on the following surfaces:
1. A flat combustible surface.
2. A raised wooden platform.
3. A concrete block or other solid object placed be-

neath each of the four (4) corners of the fireplace.

The fireplace 

must

 be spaced 1/2" (13 mm) from a 

combustible back wall and 1/2" (13 mm) from a com-
bustible side wall or support. Refer to Page 14, Figure 
18.

Planning the Chimney Run

Determine how the chimney will be run, length of run 
and chimney components required to complete the 
job. (Fig. 4)  

Never

 install a chimney below minimum 

heights.

The Ten Foot Rule

Major U.S. building codes specify a minimum chimney 
height above the roof top. The “Ten Foot Rule” is a fire 
safety rule and not a draft rule.  It is recommended that 
you always meet or exceed the “Ten Foot Rule,” espe-
cially when installing a termination on a high pitch roof.  
(Fig. 6)
The key points of the "Ten Foot Rule" are:
1. If the horizontal distance from the chimney to the peak 

of the roof is 10' (3 m) or less, the top of the chimney 
must be at least 2' (609 mm) above the peak of the 
roof, but never less than 3' (914 mm) in height above 
the highest point where it passes through the roof.

2. If a horizontal distance from the chimney to the peak 

of the roof is more than 10' (3 m), a chimney height 
reference point is established that is on the surface of 
the roof a distance of 10' (3 m) from the chimney in a 
horizontal plane. The top of the chimney must be at 
least 2' (609 mm) above the reference point, but never 
less than 3' (914 mm) in height above the highest 
point where it passes through the roof.

In planning a chimney system, it is important to know:
1.  The height of a chimney is measured from the 

hearth to the exit point on the termination.

2.  A chimney cannot be offset more than 30° from a 

vertical plane.

3.  A chimney may run straight up or it may be neces-

sary to offset it to avoid obstructions.

4.  The maximum length of an angled run (total chim-

ney system) is 20' (6 m).  

5.  No more than 2 offsets (4 total 30° elbows in U.S./

or 2 total 45° elbows in Canada) per fireplace may 
be used.

6.  A guy wire stabilizer (not provided) is required for 

chimneys extending more than 6' (1.8 m) above a 
roof line.

L1

L1

LT

MODEL SK

2 WALL 

CHIMNEY

TOTAL

LENGTH 

(LT)

INSTALLED

LENGTH 

(L1)

SK81

SK818

SK83

SK84

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

56O

"

FP288A

MBUF-INSTALLED LENGTH

Triple wall

1/28/99   djt

TRIPLE

WALL

81

818

83

84

FP288A

Fig. 5 

 Installed lengths of chimney sections.

2’ Min.

2’ Min.

3’

Min.

0 To 10’

3’

Min.

0 To 10’

AC246

4/1/96

Reference

Point

AC246

Fig. 6 

  Ten Foot Rule illustration.

Summary of Contents for CWC400

Page 1: ...se in U S Canada Underwriter s Laboratories Report No MH7603 DO NOT DISCARD THIS MANUAL Retain for future use 87D1504 12 09 Rev 4 FP583A WMC 12 18 98 CWC Series Woodburning Fireplaces Homeowner s Inst...

Page 2: ...HSC in combination or assembly with a MHSC fire place system notwithstanding any indepen dent testing laboratory or other third party ap proval of such component parts or accessory Any such action may...

Page 3: ...203mm 3 6 9 1 4 m m Fig 2 CWC500 Series specifications and framing FP592A CWC500 Series Woodburning Fireplace Circulating Model FP590A WMC36 SPECS 1 28 99 djt B 1 6 m m Z x 13mm Z x 36 914mm 35Z v 895...

Page 4: ...Outlet Grille Damper Control Gas Line Knockout both sides Screen Grate Firebox Metal Safety Strips 1 2 or 3 pieces Inlet Grille Outside Air Cover Plate Electrical Access Gas Line Access both sides Nai...

Page 5: ...1 0 0 1 0 31 60 0 1 0 1 0 34 65 0 0 2 0 0 37 70 1 1 0 1 1 41 77 0 0 1 1 1 45 83 0 1 2 0 1 47 87 0 0 0 2 1 51 94 0 1 1 1 1 53 98 0 0 3 0 1 56 103 0 1 0 2 1 59 108 0 0 2 1 1 62 113 0 1 3 0 1 64 117 0 0...

Page 6: ...2 609 mm above the peak of the roof but never less than 3 914 mm in height above the highest point where it passes through the roof 2 If a horizontal distance from the chimney to the peak of the roof...

Page 7: ...u live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of fireplace with a noncomb...

Page 8: ...tions Read all instructions before beginning installation Fol low instructions carefully The SCVS speed control may be used as an alternate wall switch in lieu of the single pole Listed 1 5 Amp 120V s...

Page 9: ...bows Use the 30 Offset Elbow table on Page 5 to determine proper offset and parts required Each offset requires two 2 elbows The second elbow is equipped with support straps It is very important to in...

Page 10: ...FP551 WF551 BR BC 9 29 97 See Fig 12 See Fig 12 Existing Ceiling Joists Ceiling New Framing Members Chimney Hole Fig 12 Ceiling chimney hole sizes necessary for installing firestop spacer Size of Chim...

Page 11: ...y snap together Once sections are snap locked in place it is extremely difficult to get them apart Make sure the pipe is firmly snapped and locked together as each pipe section is mounted When install...

Page 12: ...framing hole Nail each corner of attic insulation shield to the framing members of the ceiling hole using 8d nails Attic shields are not required at the roof Continue Installing Pipe to Complete Run C...

Page 13: ...c tions all pipes should extend Installing Top Housing or Termination Follow the installation instructions provided with the chimney termination you have selected Installing Chimney In a Chase Refer t...

Page 14: ...Wall Shield Model SP40 or a specifically built wall shield described below The special wall shield design described in Figure 19 is an alternate method of adding protection to side walls and can be u...

Page 15: ...om manufacturer of the material Fac tors are related by the formula K 1 R T given thickness R thermal resistance for a given thickness T K thermal conductivity Noncombustible material with a lower R v...

Page 16: ...d material per inch material Example of Determining Hearth Extension Equivalents To determine the thickness required for any new mate rial Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in ne...

Page 17: ...en the pipe and tube Note Gas pipe should not come in contact with any wood structures until it has reached a point at least one 1 inch away from fireplace side NOTE When installing an ANSI Z21 11 2 v...

Page 18: ...D0131 26D0131 5 Damper Knob Wood 7536177 7536177 6 Firebrick Left Side 3041104 3034102 7 Firebrick Back 3030102 3034104 8 Firebrick Right Side 3041105 3034103 9 Firebrick Hearth 3041103 3034105 10 Scr...

Page 19: ...d the coverage provided by the owner s insurance Accessories Contact your Monessen distributor or dealer for finishing Mantels available in a wide selection of styles Glass Door Optional Bi Fold door...

Page 20: ...e chimney cap used to PLTSK8 SK8 terminate chimney through a chase Includes adapter Flashing not included Chase Top Housing Square chimney cap used to terminate chimney SLTSK8 SK8 through a chase Incl...

Page 21: ...m the chimney to combustible framing With 16 center lines Attic Insulation Shield Used to prevent attic insulation from FS2100 HT 3 wall CF 11 contacting the chimney system Canada Chimney Collar Enclo...

Page 22: ...22 CWC Series Woodburning Fireplace 87D1504...

Page 23: ...re dif ferentials produced by wind Broken glass components Cracks in ceramic and castable parts that do not affect safe operation We do not warrant this fireplace to be in compliance with your local b...

Page 24: ...MHSC 149 Cleveland Drive Paris Kentucky 40361 www mhsc com...

Reviews: