Do not allow the trim materials to extend closer than 3/8 inch to the vertical edges of the firebox opening if you
plan to equip the fireplace with glass doors.
The face of your fireplace may be left exposed or trimmed. If trim is installed, be sure it is fastened securely to
the face of the fireplace. Any crack between the trim material and the face of the fireplace could pose a fire
hazard and impair the proper operation of the fireplace; seal such cracks. See Figure 31. Blocking the fireplace
with framing and attaching the base to the supporting floor will reduce the possibility of a crack redeveloping
after sealing.
(CAUTION: ACCEPTABLE COMBUSTIBLE MANTEL LOCATION SHOWN BY PART C OF
FIGURE 31 IS FOR WOODBURNING FIREPLACE INSTALLATION ONLY. SEE FIGURES 29 AND 30 FOR
ACCEPTABLE COMBUSTIBLE MANTEL LOCATIONS WHEN AN UNVENTED GAS APPLIANCE IS
INSTALLED IN THE FIREPLACE.)
26
T
RIM
I
NSTALLATION
GAS LINE PLUMBING DETAIL
CAUTION: WHEN USING A GAS
APPLIANCE, THE FIREPLACE
DAMPER MUST BE SET IN FULLY
OPEN POSITION.
REPACK INSULATION AROUND
GAS LINE WHERE IT PASSES THRU GAS
LINE ACCESS TUBE FOR
PROPER SEAL.
GAS LINE ACCESS TUBE
26" MAX.
INNER FIREPLACE WRAP
OUTER FIREPLACE WRAP
SIDE BRICK
FIREPLACE FIREBOX
HEARTH BRICK
COMBUSTIBLE MATERIALS
MAY BE LOCATED AT ZERO
CLEARANCE TO GAS LINE
BEYOND 4" FROM FIREPLACE
SIDE.
MAINTAIN 1/2" MINIMUM
AIR SPACE CLEARENCE
TO COMBUSTIBLES FOR
GAS LINE OUT TO 4" FROM
SIDE OF THE FIREPLACE.
SIDE
REFRACTORY
BRICK
BACK
REFRACTORY
BRICK
KNOCKOUT
F
IGURE
28
FINISH WALL
FRAMING
1/4"
INSTALLATION OF NON-COMBUSTIBLE FACING MATERIALS TO THE FRONT FACE OF THE FIREPLACE
COMBUSTIBLE FRAMING
MEMBERS FACING MATERIAL
TO TOP OF SPACERS.
CAUTION:
DO NOT COVER
OR RESTRICT SIDE VENT
AREAS WITH SURROUND
OR TRIM MATERIALS.
USE ONLY NON-COMBUSTIBLE
MATERIALS BELOW TOP OF SPACERS.
NON-COMBUSTIBLE
FACING MATERIAL
FIREPLACE FACE
STEEL LINTEL
(OPTIONAL)
WARNING:
THE SPACE BETWEEN THE
FACE OF THE FIREPLACE
AND THE NON-COMBUSTIBLE
FACING MATERIAL MUST BE
SEALED. FAILURE TO
PROPERLY SEAL THIS CRACK
CAN CAUSE A POSSIBLE FIRE
HAZARD AND WILL VOID THE
WARRANTY.
SCREENED OPENING
OF FIREPLACE
4"
(REF.)
EXTEND LINE FROM OPPOSITE REAR OF
FIREBOX THRU A POINT 4" IN FRONT OF
FIREPLACE FACE, AND 1" OUTSIDE OF
SCREENED OPENING.
OUTLINE OF
FIREPLACE
FIREBRICK
COMBUSTIBLE SURROUND
MATERIALS MAY BE PLACED
WITHIN SHADED AREAS.
NOTE: COMBUSTIBLE
MATERIALS MUST NOT
OVERLAP BLACK PAINTED
SURFACE MORE THAN 1/8".)
COMBUSTIBLE
FRAMING
MEMBERS
MAY BE
PLACED
ACROSS
TOP SPACERS.
12" MAX.
2 3/4" HOOD
(PART NO.
075629)
SIDE VIEW CUT-AWAY
FACING AND MANTEL CONSTRUCTION
075629 HOOD MUST
BE INSTALLED WHEN
MANTEL IS 12" FROM
FIREPLACE OPENING.
WHEN 075629 HOOD IS
INSTALLED GLASS DOORS
HAVE TO BE REMOVED.
12"
NOTE: NO COMBUSTIBLE
MATERIAL BELOW 12"
FROM OPENING
39 1/2"
44"
(MIN.)
48"
(MIN.)
1 1/2"
MAX.
COMBUSTIBLE
MANTEL AND/OR
TRIM MAY BE
PLACED WITHIN
THE SHADED AREA.
8"
TOP "V"
SPACERS
FLOOR
NON-COMBUSTIBLE
WALLBOARD
USE ONLY NON-COMBUSTIBLE MATERIALS BELOW
TOP OF SPACERS AND BEHIND FRONT FACE.
FINISH WALL
FRAMING
1/4"
INSTALLATION OF NON-COMBUSTIBLE FACING MATERIALS TO THE FRONT FACE OF THE FIREPLACE
COMBUSTIBLE FRAMING
MEMBERS FACING MATERIAL
TO TOP OF SPACERS.
CAUTION:
DO NOT COVER
OR RESTRICT SIDE VENT
AREAS WITH SURROUND
OR TRIM MATERIALS.
USE ONLY NON-COMBUSTIBLE
MATERIALS BELOW TOP OF SPACERS.
NON-COMBUSTIBLE
FACING MATERIAL
FIREPLACE FACE
STEEL LINTEL
(OPTIONAL)
WARNING:
THE SPACE BETWEEN THE
FACE OF THE FIREPLACE
AND THE NON-COMBUSTIBLE
FACING MATERIAL MUST BE
SEALED. FAILURE TO
PROPERLY SEAL THIS CRACK
CAN CAUSE A POSSIBLE FIRE
HAZARD AND WILL VOID THE
WARRANTY.
SCREENED OPENING
OF FIREPLACE
4"
(REF.)
EXTEND LINE FROM OPPOSITE REAR OF
FIREBOX THRU A POINT 4" IN FRONT OF
FIREPLACE FACE, AND 1" OUTSIDE OF
SCREENED OPENING.
OUTLINE OF
FIREPLACE
FIREBRICK
COMBUSTIBLE SURROUND
MATERIALS MAY BE PLACED
WITHIN SHADED AREAS.
NOTE: COMBUSTIBLE
MATERIALS MUST NOT
OVERLAP BLACK PAINTED
SURFACE MORE THAN 1/8".)
COMBUSTIBLE
FRAMING
MEMBERS
MAY BE
PLACED
ACROSS
TOP SPACERS.
12" MAX.
2 3/4" HOOD
(PART NO.
075629)
SIDE VIEW CUT-AWAY
FACING AND MANTEL CONSTRUCTION
075629 HOOD MUST
BE INSTALLED WHEN
MANTEL IS 12" FROM
FIREPLACE OPENING.
WHEN 075629 HOOD IS
INSTALLED GLASS DOORS
HAVE TO BE REMOVED.
12"
NOTE: NO COMBUSTIBLE
MATERIAL BELOW 12"
FROM OPENING
39 1/2"
44"
44"
(MIN.)
(MIN.)
48"
48"
(MIN.)
(MIN.)
1 1/2"
1 1/2"
MAX.
MAX.
COMBUSTIBLE
COMBUSTIBLE
MANTEL AND/OR
MANTEL AND/OR
TRIM MAY BE
TRIM MAY BE
PLACED WITHIN
PLACED WITHIN
THE SHADED AREA.
THE SHADED AREA.
8"
TOP "V"
TOP "V"
SPACERS
SPACERS
FLOOR
FLOOR
NON-COMBUSTIBLE
NON-COMBUSTIBLE
WALLBOARD
WALLBOARD
USE ONLY NON-COMBUSTIBLE MATERIALS BELOW
USE ONLY NON-COMBUSTIBLE MATERIALS BELOW
TOP OF SPACERS AND BEHIND FRONT FACE.
TOP OF SPACERS AND BEHIND FRONT FACE.
F
IGURE
30
F
IGURE
29
F
IGURES
29
AND
30
SHOW
ACCEPTABLE
COMBUSTIBE
MANTEL
LOCATIONS
IF
AN
UNVENTED
GAS
APPLIANCE
IS
INSTALLED
IN
THE
FIREPLACE
. S
EE
P
ART
C
OF
F
IGURE
31
FOR
ACCEPTABLE
COMBUSTIBLE
MANTEL
LOCATION
IF
FIREPLACE
IS
INSTALLED
TO
BURN
WOOD
.
53D9031. Rev 1 03/03
Summary of Contents for BWB400 Series
Page 38: ...38 NOTES This page intentionally left blank 53D9031 Rev 1 03 03...
Page 39: ...NOTES 39 This page intentionally left blank 53D9031 Rev 1 03 03...
Page 78: ...38 THIS PAGE INTENTIONALLY LEFT BLANK 53D9032 Rev 1 03 03...
Page 79: ...39 THIS PAGE INTENTIONALLY LEFT BLANK 53D9032 Rev 1 03 03...