EtherNet/IP™ CIP Safety™ IP67 HarshIO 600
20
IP67 Safety Digital I/O Modules
Explosive environments
Danger!
This device is not certified for applications in
explosive environments (EX-zone)
Power supply and Electrical safety
The device is developed for operation on 24 VDC power supplies, which correspond to the PELV-/SELV
regulations in accordance to EN 50178.
Risk of injury by electric current!
There may only devices be connected to the module, which have a safe separation
from the mains (such as 120V/230V/600V) power.
The power supply to generate 24 V power must correspond to the requirements for
PELV/SELV according to EN 50178.
IP67 rating
The product complies with IP67 when installed. All caps of non-used connectors shall be mounting on the
product to maintain the IP67 rating during operation.
Danger!
Risk of electric power!
Contact with live parts is immediate danger to life.
Mission time
The expected life time of the HarshIO module is up to 20 years with no proof test necessary.
Warning!
If the user calculates their safety application with the specified data for >20
years, the
HarshIO has to be decommissioned and replaced. A proof test cannot be established
by the user.
Earthing
Warning!
Connections to earth shall be wired accordingly to the relevant chapter of this manual in
order to warrant EMC characteristics of the product.