MOHAWK V-A SERIES: VERTICAL RISE DRIVE-ON MANUAL
35,000 - 64,000 LB MODEL
4-8
4.5.3.
Electric connection
A) LIFT SUPPLY
The electric supply system must include:
a main switch with a circuit breaker;
fuses or thermal magnet protection suited to the machine's
characteristics;
device against accidental contact, for protection.
The switch must be positioned in the immediate vicinity of the machine in
full compliance with local accident prevention regulations.
Power cables must have a suitable section for absorbing current, without
deviations for other utilities.
Electric systems must be created according to the state of the art by a
qualified electrician who must check the earthing system's efficiency.
The power cable must be locked in the dedicated cable gland and the
electric panel must be carefully closed to assure the envisaged IP 54
protection.
Only connect the machine to type approved sockets with an earth cable
of proven efficiency.
Periodically have qualified personnel check the correct tightening of the
electric cables of the various components.
Power cables must have a suitable section for absorbing current,
without deviations for other utilities
Electrical system shall be designed to meet all local / national
codes and shall be properly grounded
Attention:
power the lift's electrics system using a line fitted with a mains switch
and without any other junctions.
The devices fitted to provide protection against short circuits must
take into account the features of the electrical equipment:
NOMINAL POWER
HP
10
10
10
10
10
10
VOLTAGE
V
200
208
220-
240
380-
415
440-
480
550-
575
No. of phases
3
3
3
3
3
3
FREQUENCY
Hz
60
60
60
60
60
60
NOMINAL CURRENT
A
32.2
30.8
28.0 18.0 14.0
11.0
PICKUP CURRENT
A
193.2 184.8 168.0 108.0 84.0
66.0
PRO
TECTI
O
N
FUSE (DELAYED)
A
35
35
35
25
25
25
FUSE (FAST)
A
50
50
50
35
35
35
THERMOMAGNET
A
50
50
50
32
32
32
B) LIFT AND CONSOLLE WIRING
The wire of the cables connecting the lift and the consolle are
numbered.
Connect the wire to the terminal box of the console according
to the wiring diagram.
Install methalic covers for piping and cables
Summary of Contents for V-035-A-X
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 14: ......
Page 22: ...MV A00000920 MOHAWK V A SERIES VERTICAL RISE DRIVE ON MANUAL 35 000 64 000 LB MODEL 3 8 LIFT ...
Page 28: ......
Page 38: ...MV A00000920 MOHAWK V A SERIES VERTICAL RISE DRIVE ON MANUAL 35 000 64 000 LB MODEL 4 10 ...
Page 60: ......
Page 61: ...MV A00000920 MOHAWK V A SERIES VERTICAL RISE DRIVE ON MANUAL 35 000 64 000 LB MODEL 7 1 ...