POSITION VALVE IN PIPING
Verify that the valve and actuator / handlever
orientation is correct .
Verify that the valve is in the
open
position to prevent
any damage to the ball surface from debris .
Position the valve in line with mating flanges .
Note:
Support or lift as required, using lifting lugs or nylon straps around the
valve body. Do not lift or support by the actuator alone.
CAUTION!
All welding / grinding debris must be thoroughly
flushed from all associated piping before valve is
installed .
THIS WILL AFFECT THE VALVE WARRANTY .
IDENTIFY SEALING DIRECTION
Identify the preferred sealing direction of the valve,
indicated by
Pressure End
indicated on the valve
body
02
.
Note:
The normal direction of flow is from the higher pressure end (upstream)
to lower pressure end when the valve is
closed
.
In certain conditions, proper operation may require the indicated flow be
opposed to the line flow. Make sure that the
Pressure End
is positioned
toward the highest pressure against the valve in the
closed
position.
SECURE VALVE IN PLACE
Install flange gaskets and bolting per customer
requirements .
Note:
MOGAS valve flanges are supplied in the customary “straddle centerline”
hole orientation, unless otherwise specified.
VERIFY OPERATION
After installation,
open
and
close
several times to
ensure smooth operation .