Hardware
Device Description Embedded HMI XVH-3x0
Mounting Instructions
01/05 AWB2776-1559GB
© by Moeller GmbH
21
10
M
OUNTING
I
NSTRUCTIONS
10.1 G
ENERAL MOUNTING INSTRUCTIONS
All devices are mounted from the front, i.e. in a control panel.
Standard front
The device is fixed from the rear with 4 fixing brackets (M4 threaded pin with type 2 hexagon). Four
additional fixing brackets are required for mounting to IP 65.
The devices can be run at a maximum ambient temperature of 50°C. This refers to the area directly
next to the lower cooling slots when the device is mounted vertically. A clearance of 3 cm must be
maintained at the cooling slots to ensure unobstructed air convection.
Hot components such as a heavily loaded transformer must have a clearance of at least 15 cm.
Avoid the exposure of the flat screen to direct sunlight. The sunlight (UV component) reduces the
lifespan of the LCD crystals.
The temperature inside the XVH can be scanned via the Control Panel.
Î
Further information: PANEL with WindowsCE [3]
The cooling slots must always be free in order to ensure the proper cooling of the
system.
Avoid the exposure of the flat screen to direct sunlight.
Ensure that operating elements (Control button, CF card) and terminals are still
accessible when the device is mounted.
The front panel should not exceed a maximum thickness of 5 mm, due to the
clamping range of the fixing brackets.