4.2 G
ENERAL NOTES ON CABLING
Cabling should be carried out with special care in order to ensure
interference-free operation.
The EMC values stated in the technical data can only be guaranteed if the
connections and cables are prepared according to the specifications stated.
The cabling must be laid separately from low-voltage cables or isolated with
double or reinforced insulation.
Î
Further information: Installation instructions, General wiring instructions [1]
4.3 C
ONNECTION TO THE POWER SUPPLY
System supply
24 VDC SELV (safety extra low voltage)
Not isolated
Current consumption
Î
Chapter 15
Fuse / protection
Internal fuse / protection against reverse polarity
Housing potential
Connected to 0 V terminal
Terminal type
Screw terminal (screwdriver No. 3), pluggable
Cross section
min. 0.75 mm
2
/ max. 2.5 mm
2
(lead or wire)
min. AWG24 / max. AWG12
Stripping length
7 mm
Î
Further technical data: Chapter 15
Plug connector: Phönix MSTB 2.5/3-ST-5.08
Phönix Order No. 1757022;
Supplied with unit
(view from the wiring side)
+24 VDC
+24 VDC power supply
GND
Functional ground, connected with housing (connection not compulsory)
0 V
0 V power supply (connected with housing)
+24 VDC GND 0 V