![Moeller ps4-201-mm1 Hardware And Engineering Download Page 85](http://html1.mh-extra.com/html/moeller/ps4-201-mm1/ps4-201-mm1_hardware-and-engineering_1819300085.webp)
Technical Data
81
04/
99 AW
B
27-
1184 G
B
Galvanic isolation
Yes
Galvanic isolation between inputs
No
Input status indication
Yes (LEDs)
Terminals
Plug-in screw terminals
Conductor cross-section
Flexible with ferrules
0.22 to 1.5 mm
2
Solid
0.22 to 2.5 mm
2
High-speed counter input
I0.0
Clock frequency
3 kHz
Pulse shape
Square
Pulse duration
50 %
Edge duration
≤
3 %
Alarm input
I0.1
Analog inputs
No.
2
Signal range
0 V to 10 V
Total error
Normally 0.8% of full scale
No. of conversions
1
⫻
per cycle
Input resistance
20 k
Ω
Connection type of signal transmitter Two-wire connection to
transmitter
Digital representation of input signal
10 bits (1024 increments)
Setpoint potentiometers
No.
2
Value range
10 bits (1024 increments)
Adjustment
With screwdriver
Summary of Contents for ps4-201-mm1
Page 4: ...II 04 99 AWB 27 1184 GB...
Page 36: ...32 04 99 AWB 27 1184 GB...
Page 52: ...48 04 99 AWB 27 1184 GB...
Page 58: ...54 04 99 AWB 27 1184 GB...
Page 74: ...70 04 99 AWB 27 1184 GB...
Page 88: ...84 04 99 AWB 27 1184 GB...