![Moeller ps4-201-mm1 Hardware And Engineering Download Page 56](http://html1.mh-extra.com/html/moeller/ps4-201-mm1/ps4-201-mm1_hardware-and-engineering_1819300056.webp)
Slave Addressing
52
04/
99 AW
B
27-
1184 G
B
The general syntax rule is as follows:
Operand-data type-line-station-module-byte-bit
Example
The PS4-200 (master) exchanges word data with an
intelligent slave. You can define the number of send
and receive bytes when you set the station
parameters in the Sucosoft S 40 Topology
Configurator (see chapter 4, “Software
Configuration”).
Figure 24: Configuration example for sending and receiving
communication data to/from an intelligent slave
If the PS4-200 is run as slave, it provides status
bytes %ISB0.0.0.0 for device status information
and %ISB0.0.0.1 for slave status information.
These status bytes cannot be scanned together
in one word but must be addressed separately.
PS 4-201-MM1
PS 4-151-MM1
햲
햳
RD
SD
RD
SD
Line 1
Station 1
Master
Slave