![Moeller ps4-201-mm1 Hardware And Engineering Download Page 44](http://html1.mh-extra.com/html/moeller/ps4-201-mm1/ps4-201-mm1_hardware-and-engineering_1819300044.webp)
Software Configuration
40
04/
99 AW
B
27-
1184 G
B
Table 3: Interface parameter settings for serial
communication via the RS 485 interface
Line:
Number of the network line to which a station is
connected. The master is always connected to line 0
and the slaves to line 1.
Station:
Number of the station connected to a line
Module:
Number of the module belonging to a station
Baud rate:
Select 375 kBaud as the data transfer rate if only
Suconet K stations are connected to the Suconet K
line. The internal plausibility checks of Sucosoft S 40
will automatically set the baud rate of the line to
187.5 kBaud if the line includes Suconet K1 stations.
The following baud rates are available for serial
communication via the SCO function block: 300,
600, 1200, 2400, 4800, 9600, 19200 baud.
Protocol:
The following interface parameters can be defined
for serial data exchange with a partner device via the
Suconet K interface. These settings must be
identical to those on the partner device.
Start bit
Stop bit
Data bit
Parity
1
1
8
–
1
1
8
even
1
1
8
odd
1
2
8
–
Summary of Contents for ps4-201-mm1
Page 4: ...II 04 99 AWB 27 1184 GB...
Page 36: ...32 04 99 AWB 27 1184 GB...
Page 52: ...48 04 99 AWB 27 1184 GB...
Page 58: ...54 04 99 AWB 27 1184 GB...
Page 74: ...70 04 99 AWB 27 1184 GB...
Page 88: ...84 04 99 AWB 27 1184 GB...