![Moeller ps4-201-mm1 Hardware And Engineering Download Page 28](http://html1.mh-extra.com/html/moeller/ps4-201-mm1/ps4-201-mm1_hardware-and-engineering_1819300028.webp)
Engineering
24
04/
99 AW
B
27-
1184 G
B
Legend for Figure 11:
Main switch
Protective device for power supply units
Miniature circuit-breakers
Power supply for the digital inputs
Link (no longer required from PS4-200 version 04)
Power supply for the PS4-200
Power supply for the digital outputs
Reference potential for the digital inputs/outputs
Terminal with PE connection
(no longer required from version 04)
Connect top-hat rail to mounting plate (galvanized
sheet steel) with a low impedance connection over a
large surface and with protection against corrosion.
Maintain a clearance of at least 30 cm (12
″
)
between the analog cable and the power supply
cables.
Do not lay the 0 V of the analog signals together
with the 0 V of the PS4-200 and the 0 V of the
digital inputs/outputs.
Ensure that the analog actuators and
transmitters are galvanically isolated. If potential
isolation is not sufficient, the manufacturers of
the analog transmitters and actuators can
provide suitable filters.