Technical data

 

Control circuit 

 min. 

typ. 

max. 

Rated voltage U

ESR4-NE-42 AC/DC 20.4 

AC/DC 24 V 

AC/DC 26.4 V 

Rated voltage U

ESR4-VE3-42 DC 20.4 

DC 24 V 

DC 26.4 V 

DC  

1.0 

 

Rated power 

AC 

 

1.5 W / 2.7 VA 

 

Residual ripple DC 

 

 

2.4 V

SS

 

Rated frequency AC 

50 Hz 

 

60 Hz 

Rated current / peak current 

 

65 mA / 1000 mA 

80 mA / 1800 mA 

Operate time t

A

  

 

20 ms 

 

Release time t

R2

 ESR4-NE-42 

 

40 ms 

 

Minimum switch-on duration t

M

 ESR4-VE3-42 

75 ms 

 

 

Release time t

R1

 ESR4-VE3-42 

3 s 

Check-back current path Y1/Y2 

1 NC, positively driven 

Rated switching voltage U

n

 

DC 24 V 

Max. continuous current I

n

 0.1 

Contact material 

Ag-alloy, gold-plated 

 

 

Output circuits 

Enabling current paths  

4 NO contacts, positively driven

 

Rated switching voltage U

n

 

AC 230 V /  DC 300 V 

Max. continuous current I

/ max. total current 

6 A / 12 A  

Utilization category according to DIN EN 60947-5-1:2005-09-

00 

AC-15: Ue 230 V, Ie 6A (3600 h

-1

)  DC-13: Ue 24 V, Ie 3A (3600 h

-1

DC-13: Ue 24 V, Ie 6 A (360 h

-1

Mechanical service life 

10 x 10

6

 switching operations

 

Contact material 

Ag-alloy, gold-plated

 

Signalling current paths  

2 NC, positively driven 

Rated switching voltage U

n

 

AC 230 V /  DC 300 V 

Max. continuous current I

 2 

Contact material 

Ag-alloy, gold-plated

 

 

 

General data 

Clearance/creepage distance between circuits 

DIN EN 60664-1 

Overvoltage category 

III 

Rated impulse withstand level 

4 kV 

Rated voltage 

AC 300 V 

Contamination level of device: inside / outside 

2 / 3 

Climatic application class 

H V G to DIN 40040: 04.87 

Protection class to DIN EN 60529: housing / terminals 

IP 40 / IP 20 

Ambient / storage temperature 

-25  ...  +55 / -25  ...  +75 °C 

Weight  

0.2 kg 

 

 

Terminals and connection 

Single-core or finely stranded 

1 x 0.14 mm² to 2.5 mm²       2 x 0.14 mm² to 0.75 mm² 

Stripping length 

max. 8 mm 

Finely-stranded with wire-end ferrule to DIN 46228 

1 x 0.25 mm² to 2.5 mm²       2 x 0.25 mm² to 0.5 mm² 

Max. tightening torque 

0.5 to 0.6 Nm 

 

 

5

 

 

Operating Instruction 

 

ESR4-NE-42, ESR4-VE3-42

 

 

Expansion device for safety switching devices 

• 

Expansion device to DIN EN 60204-1 and DIN EN 954-1 

• 

Single or two-channel control 

• 

4 enabling current paths 

• 

2 signalling current paths 

• 

1 check-back current path 

• 

ESR4-VE3-42 with OFF-delay time and time back-up 

 

 

 

 

 

 

 

 

K1

K2

13

A1

23

Y1

33

Y2

61

51

43

14

44

24

52

34 62

A2

ESR4-NE-42

 

Front View  

K1   LED green   Relay K1 

K2   LED green   Relay K2 

 

 

 

Safety Instructions 

Only trained professional electricians may 

install, startup, modify, and retrofit this 

equipment! Disconnect the device / system from 

all power sources prior to starting any work! If 

installation or system errors occur, line voltage 

may be present at the control circuit in devices 

without DC isolation! 

Observe all electrical safety regulations issued 

by the appropriate technical authorities or the 

trade association. The safety function can be 

lost if the device is not used for the intended 

purpose. Opening the housing or any other 

manipulation will void the warranty. 

 

 

Caution! 

If the device has been subjected to improper or 

incorrect use it must no longer be used, and the 

guarantee loses its validity. Impermissible 

conditions include: 

strong mechanical stress, for example through a 

fall, or voltages, currents, temperatures or 

humidity outside of the specifications. 

Before starting up your machine/plant for the 

first time, please be sure to check all the safety 

functions according to valid regulations, and 

observe the specified test cycles for safety 

equipment. 

 

 

Caution! 

Perform the following precautionary steps prior 

to installation, assembly, or disassembly: 

1.  Disconnect supply voltage to the equipment 

/ system prior to starting any work! 

2. Lockout/tag 

the 

equipment / system to 

prevent accidental activation! 

3. Confirm 

that 

no 

voltage is present! 

4.  Ground the phases and short to ground! 

5. Protect 

against 

adjacent live components 

using guards and barriers!  

6.  The devices must be installed in a cabinet 

with a protection class of at least IP 54. 

 

 

Caution! 

Limited contact protection! Protection type 

according to DIN EN 60529. 

Housing/terminals: IP 40/ IP 20.  

Finger-proof acc. to DIN VDE 0660 Part 514. 

 

Device and Function Description 

ESR4-NE-42  The supply voltage for the unit is lead by one of the output enabling current paths of the 

basic unit connected to it. After the supply voltage is applied, the relays K1 and K2 switch into their operat-

ing position. After this switch - on phase the four safety output contacts 13/14, 23/24, 33/34, 43/44 (ESR4-

NE-42) or 17/18, 27/28, 37/38, 47/48 (ESR4-VE3-42) close and the feedback contact Y1/ Y2 opens. The 

status of relays K1 and K2 is indicated by two LEDs. If the E - Stop button is pressed the enabling current 

paths of the basic unit open and the relays K1 and K2 of the ESR4-NE-42 are de - energized. The safety 

output contacts open and the feedback contact closes. The feedback contact Y1/ Y2 prevents the re - 

activation of the basic unit in case the relay K1 or K2 should not be de - energized.  

 

ESR4-VE3-42  The function corresponds to the one of the ESR4-NE-42. The ESR4-VE3-42 is available 

with OFF - delay time 3 s. The item has a time back - up, so that in case of failure of the external power 

supply the internal relays K1 and K2 stay energized until the OFF - delay time t

R1

 has elapsed. Upon timing 

- out the relays K1 and K2 go back into their off - position. The OFF - delay times > 0 s correspond to Stop 

Category 1. 

 

Proper Use 

The device is only to be used as an expansion device for safety switching devices.  

 

Notes 

• 

The actual Safety and Stop Category of the device always depends from the corresponding 

category reached by the connected basic unit. The Safety and Stop Category of the expansion 

unit can only reach the max. Safety and Stop Category of the basic unit. 

• 

The ESR4-VE3-42 can be used max. to safety category 3 acc. DIN EN 954-1. 

• 

The expansion device can be connected to one or two safety contacts of the basic unit 

according to the safety level requested. 

• 

The device can be combined with all basic safety switching devices. The feedback circuit  

Y1/Y2 of the device has to be connected to the RESET or to the feedback circuit of the basic 

unit. 

• 

Insulation on external wiring should not be cut back more than 8 mm. 

• 

External fuse protection for the relay and the contacts should not exceed 6 A type gG. 

• 

If sensors with reed contacts or semiconductor outputs used pay attention to the peak current (see 

technical data section control circuits). 

 

 

Please observe instructions from safety authorities. 

 

 

 

Summary of Contents for ESR4-NE-42

Page 1: ...Sie die Maschine Anlage gegen Wiedereinschalten 3 Stellen Sie die Spannungsfreiheit fest 4 Erden Sie die Phasen und schlie en Sie diese kurz 5 Decken und schranken Sie benachbarte unter Spannung steh...

Page 2: ...4 LED K1 LED K2 51 52 61 62 tA Ansprechzeit tR2 R ckfallzeit Funktionsdiagramm ESR4 VE3 42 A1 A2 Versorgungsspannung Y1 Y2 R ckmeldepfad 17 18 27 28 37 38 47 48 LED K1 LED K2 55 56 65 66 tA Ansprechze...

Page 3: ...ldepfad ffner f r die Kopplung zum Basisger t 4 Versorgungsspannung 1 13 23 14 24 33 34 43 44 2 52 A1 A2 L1 L 4 3 Y2 Y1 62 51 61 K1 M N K2 ESR4 VE3 42 1 4 Freigabestrompfade Schlie er 2 2 Meldestrompf...

Page 4: ...1 2005 09 00 AC 15 Ue 230 V Ie 6A 3600h 1 DC 13 Ue 24 V Ie 3A 3600h 1 DC 13 Ue 24 V Ie 6 A 360 h 1 Mechanische Lebensdauer 10x106 Schaltungen Kontaktwerkstoff Ag Legierung vergoldet Meldestrompfade 2...

Page 5: ...le through a fall or voltages currents temperatures or humidity outside of the specifications Before starting up your machine plant for the first time please be sure to check all the safety functions...

Page 6: ...44 LED K1 LED K2 51 52 61 62 tA Response time tR2 Release time Function diagram ESR4 VE3 42 A1 A2 Supply voltage Y1 Y2 Feedback circuit 17 18 27 28 37 38 47 48 LED K1 LED K2 55 56 65 66 tA Response t...

Page 7: ...control contacts 3 1 NC feedback circuit contact 4 Supply voltage 1 13 23 14 24 33 34 43 44 2 52 A1 A2 L1 L 4 3 Y2 Y1 62 51 61 K1 M N K2 ESR4 VE3 42 1 4 NO safety contacts 2 2 NC control contacts 3 1...

Page 8: ...ng to DIN EN 60947 5 1 2005 09 00 AC 15 Ue 230 V Ie 6A 3600 h 1 DC 13 Ue 24 V Ie 3A 3600 h 1 DC 13 Ue 24 V Ie 6 A 360 h 1 Mechanical service life 10 x 106 switching operations Contact material Ag allo...

Page 9: ...rzed uruchomieniem maszyny urz dzenia po raz pierwszy nale y sprawdzi wszystkie funkcje bezpiecze stwa zgodnie z obowi zuj cymi przepisami i przestrzega zdefiniowanych cykli test w dla wyposa enia bez...

Page 10: ...ny czas za czenia tR1 Czas op znionego wy czenia Schematy przy czania ESR4 NE 42 ESR4 VE3 42 Instalowanie ESR4 NE 42 Zainstaluj urz dzenie zgodnie ze schematem przy czania 1 4 styki bezpiecze stwa NO...

Page 11: ...d ca kowity 6 A 12 A Kategoria stosowania wg DIN EN 60947 5 1 2005 09 00 AC 15 Ue 230 V Ie 6A 3600 h 1 DC 13 Ue 24 V Ie 3A 3600 h 1 DC 13 Ue 24 V Ie 6 A 360 h 1 Trwa os mechaniczna 10 x 106 operaji Ma...

Page 12: ...sembly Demonta 3 3 3 Relais in Pfeilrichtung herunterdr cken Push relay down in direction of arrow Wcisnij przeka nik zgodnie z kierunkiem srza ki 4 4 4 Im heruntergedr ckten Zustand Relais in Pfeilri...

Reviews: