27
recognize this number and store it as administrator (TEL1). The administrator will
receive a confirmation SMS text message including the security code. This code is
needed to program the other settings in the unit.
NB: For this way of programming the number recognition in the administra
tor’s
phone must
be ‘on’. To program or change the administrator’s number by SMS
command, please refer to the next section.
6.4 PROGRAM THRESHOLD VALUES FOR THE TEMPERATURE
A separate high and/or low temperature limit can be set for the temperature
sensor(s). All limits can be set between -35 ºC and +70 ºC with one decimal.
Negat
ive values are entered by placing a “-” in front of the value.
To enter a temperature limit, be sure the Mobeye CML2255 is in program mode.
Send an SMS text message to the unit with following content:
SMS command lower limit sensor 1:
1111 LTL1:
example:
1111 LTL1:-5
SMS command upper limit sensor 2:
1111 HTL1:
example:
1111 HTL1:25,5
(similar for second sensor with LTL2 and HTL2)
Please mind the space behind 1111.