'20 • PAC-SM-351
Operation data can be checked with remote control unit operation.
➀
Press the
button.
The display change “
”
➁
Press the
(SET) button while “
” is
displayed.
➂
When only one indoor unit is connected to remote control,
“
” is displayed (blinking indication during
data loading).
Next, operation data of the indoor unit will be displayed.
Skip to step
➆
.
➃
When plural indoor units is connected, the smallest address
number of indoor unit among all connected indoor unit is
displayed.
[Example]:
“
” (blinking 1 seconds)
➝
“
” blinking.
➄
Select the indoor unit number you would like to have data
displayed with the
button.
➅
Determine the indoor unit number with the
(SET)
button.
(The indoor unit number changes from blinking indication
to continuous indication)
“
” (The address of selected indoor unit is blinking
for 2 seconds.)
“
” (A blinking indication appears while data loaded.)
Next, the operation data of the indoor unit is indicated.
➆
Upon operation of the
button, the current operation data is displayed in order from data number 01.
The items displayed are in the above table.
*Depending on models, the items that do not have corresponding data are not displayed.
➇
To display the data of a different indoor unit, press the
button, which allows you to go back to the
indoor unit selection screen.
➈
Pressing the
button will stop displaying data.
Pressing the
(RESET) button during remote control unit operation will undo your last operation and allow you
to go back to the previous screen.
If two (2) remote controls are connected to one (1) inside unit, only the master control is available for trial
operation and confirmation of operation data. (The slave remote control is not available.)
Models FDC100, 125, 140VNX-W, 100, 125, 140VSX-W
ە
Number 33 details of compressor protection status
No.
Contents of display
Reference page
"0" Normal
"1" Discharge pipe temperature protection control
P.45
䠈䠄㻢䠅
.(a).(i)
"2" Discharge pipe temperature anomaly
P.45
䠈䠄㻢䠅
.(a).(ii)
"3" Current safe control of inverter primary current
P.47
䠈䠄㻢䠅
.(f)
"4" High pressure protection control
P.45
䠈䠄㻢䠅
.(b).(i)
䠈
P.46
䠈䠄㻢䠅
.(c).(i)
"5" High pressure anomaly
P.45
䠈䠄㻢䠅
.(b).(ii)
"6" Low pressure protection control
P.46
䠈䠄㻢䠅
.(e).(i)
䚷
"7" Low pressure anomaly
P.46
䠈䠄㻢䠅
.(e).(ii)
"8" Anti-frost prevention control
P.47
䠈䠄㻢䠅
.(j)
"9" Current cut
P.47
䠈䠄㻢䠅
.(f)
"10" Power transistor protection control
P.47
䠈䠄㻢䠅
.(g)
"11" Power transistor anomaly (Overheat)
P.47
䠈䠄㻢䠅
.(h)
"13" Spare
"14" Dewing prevention control
P.48
䠈䠄㻢䠅
.(k)
"15" Current safe control of inverter secondary current P.47
䠈䠄㻢䠅
.(f)
"16" Stop by compressor rotor lock
"17" Stop by compressor startup failure
P.48
䠈䠄㻢䠅
.(o)
"18" Active filter anomaly
Note(1) Operation data display on the remote control.
䞉
Data is dispalyed until canceling the protection control.
䞉
In case of multiple protections controlled, only the younger No. is displayed.
Note(2) Common item.
䐟
In heating mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "4" is displayed.
䐠
In cooling and dehumidifying mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "8" is displayed.
Refer to page 73.
Number
01
02
03
04
05
06
07
08
09
10
11
12
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
Data Item
(Operation Mode)
(Set Temperature)
(Return Air Temperature)
(Remote Control Temperature Sensor)
(Indoor Heat Exchanger Temperature Sensor / U Bend)
(Indoor Heat Exchanger Temperature Sensor /Capillary)
(Indoor Heat Exchanger Temperature Sensor /Gas Header)
(Indoor Unit Fan Speed)
(Frequency Requirements)
(Response Frequency)
(Pulse of Indoor Unit Expansion Value)
(Total Running Hours of The Indoor Unit)
(Outdoor Air Temperature)
(Outdoor Heat Exchanger Temperature Sensor)
(Outdoor Heat Exchanger Temperature Sensor)
(Compressor Frequency)
(High Pressure)
(Low Pressure)
(Discharge Pipe Temperature)
(Compressor Bottom
Temperature)
(Current)
(Target Super Heat)
(Super Heat)
(Discharge Pipe Super Heat)
(Protection State No. of The Compressor)
(Outdoor Unit Fan Speed)
(63H1 On/Off)
(Defrost Control On/Off)
(Total Running Hours of The Compressor)
(Pulse of The Outdoor Unit Expansion Valve EEVC)
(Pulse of The Outdoor Unit Expansion Valve EEVH)
(b) In case of RC-E5 remote control
Summary of Contents for SRK100VNXWPZSX
Page 181: ...180 20 PAC SM 351 1 e SRK series PHA012D402...
Page 182: ...181 20 PAC SM 351 Screw...
Page 183: ...182 20 PAC SM 351 3 PHA012D402...
Page 184: ...183 20 PAC SM 351 4 PHA012D402...