150
-
'20 • PAC-SM-351
E14
Communication error
between master and slave indoor units
–
–
Keeps flashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is it
OK the unit
address setting for master
and slave interface
kit?
NO
YES
Is
the remote
control wiring between
interface kit
defective?
YES
NO
Is
the interface
kit wiring between
indoor units
defective?
Is it
restored by resetting the
power source?
Note (1) Set dip switches SW3-1 and SW3-2 as shown in the following table.
(Factory default setting – “Master”)
Master
Slave1 Slave2
SW3-1
OFF
OFF
ON
SW3-2
OFF
ON
OFF
Dip
switch
Interface kit
YES
NO
NO
YES
Correct unit address setting.
Correct wiring.
Correct wiring.
Defective indoor unit
control PCB Replace.
• Malfunction by noise
• Check surrounding
environment.
2. Error detection method
When communication error
between master and slave indoor
units occurs
3.
Condition of error displayed
Same as above
4. Presumable cause
• Unit address setting error
• Broken remote control wire
• Defective remote control wire
connection
• Broken interface kit wire
• Defective interface kit wire
connection
• Defective indoor unit control
PCB
Note:
Error code
Remote control:
Indoor
display
RUN light TIMER light
Green LED Red LED
Outdoor unit
control PCB
Content